USING THE KP02 MAINTENANCE CONTROL DISPLAY
LIST OF SETPOINTS (LF 20 - APRIL 2002) - cont'd
1st Level
[Safety limits] Room relative humidity low limit (in %) - Threshold of
C 041
activation of the safety cut-out
[Limit safety] Room absolute humidity low limit (in g/kg) - Threshold of
C 042
activation of the safety cut-out
[Safety limits] Room relative humidity high limit (in %) - Threshold of
C 043
activation of the safety cut-out
[Limit safety] Room absolute humidity high limit (in g/kg) - Threshold
C 044
of activation of the safety cut-out
[Anticipation function] Bottom of slope (in °c) - Limit of activation of
C 045
the function - This allows an anticipated start-up in the morning mode
depending on the outside temperature.
[Anticipation function] Slope - Number of minutes of anticipation per
C 046
degrees. This allows an anticipated start-up in the morning mode
depending on the outside temperature.
C 047
[Co²] Fresh air dampers opening threshold (in ppm)
C 048
[Co²] Fresh air dampers maximum opening limit (in ppm)
[Extraction] Threshold of activation of the power exhaust fan
C 049
according to the position of the economiser damper (in %)
2nd Level
[kp17] [Mode] Maximum limit for room temperature, Day mode (in °c)
C 050
- (active for the mode Day)
[kp17] [Mode] Minimum limit for room temperature, Day mode (in °c) -
C 051
(active for the mode Day)
C 052
[Room control] Minimum operation time for a stage (in seconds)
[Room control] Temperature difference between the beginning and
C 053
the end of a stage of control in cooling. (in °c)
[Room regulation] Temperature difference between two stages of
C 054
control in cooling. (in °c)
[Room control] Temperature difference between the beginning and
C 055
the end of a stage of control in heating. (in °c)
[Room control] Temperature difference between two stages of control
C 056
in heating. (in °c)
[Room control] Choice of the priority for the control in heating.
C 057
[On] Hot water coil or electrical heater or gas then compressors
[Off]. Compressors then hot water coil or electrical heater or gas
[Supply control] Activation of the control. – The control of the supply
C 058
applies when the room temperature is in the dead zone. - This
function allows to maintain comfort with the supply air
C 059
[Supply control] Sampling time (in seconds)
[Supply control] Choice of the priority for the control in heating
C 060
[On] Hot water coil or electrical heater or gas then compressors
[Off] Compressors then hot water coil or electrical heater or gas
Page 64 - IOM / ROOF-TOP FLEXY™ Series
Mini.
Factory
0 %
0 %
0.0 g/kg
0.0 g/kg
30.0 g/kg
50 %
100 %
0.0 g/kg
30.0 g/kg
30.0 g/kg
0.0 c
10.0 c
0
0
0 ppm
1000 ppm
2000 ppm
0 ppm
1500 ppm
2000 ppm
0 %
10%
Mini.
Factory
21.0 c
27.0 c
8.0 c
17.0 c
25 s
180 s
0.0 c
1.0 c
0.1 c
1.0 c
0.0 c
0.5 c
0.1 c
0.5 c
Off
Off
Off
Off
1 s
10 s
Off
Off
Maxi.
50 %
100 %
20.0 c
100
100 %
Maxi.
35.0 c
21.0 c
1800 s
10.0 c
10.0 c
10.0 c
10.0 c
On
On
120 s
On