SAFETY AND ERROR CODES
111
121
131
141
112
122
132
142
113
123
133
143
115
125
135
145
117
127
137
147
Page 122 - IOM / ROOF-TOP FLEXY™ Series
Refrigeration system faults
Faulty condenser temperature sensor
Faulty pressure transmitter sensor, refrigeration system
Faulty refrigeration system, frost temperature sensor
High pressure switch safety or compressor electrical safety
The compressor contactor is not connected although the CLIMATIC™ requests it.
- The high pressure pressostat is open.
- The internal protection of the compressor motor is open.
The high pressure pressostat and the compressor motor thermal protection act directly on the
compressor contactor. This information is transmitted to the CLIMATIC™ via an auxiliary contact
of the contactor.
If the CLIMATIC™ gives the order to operate to the compressor and if the auxiliary contact is
still open 5 seconds later, the fan safety system is activated and stops the compressor.The
safety system automatically cuts out after 4 minutes.
It is also automatically locked out after 3 failures within a day. In this case, manual resetting is
obligatory. The counter is reset to zero every evening at 20:00 if its value does not exceed 3
failures.
Faulty low pressure compressor
If the low pressure pressostat is open and the compressor has been operating for more than 2
minutes, the low pressure safety system is activated and stops the compressor. This safety
system is not taken into account during the defrost cycle for the heat pump units.
The compressor is engaged when the pressostat contact closes.
It is also automatically locked out after 3 failures within a day. In this case, manual resetting is
obligatory. The counter is reset to zero every evening at 20:00 if its value does not exceed 3
failures.