Module ID Code
1
Preliminary Operating Considerations
This chapter explains how the analog input module and the SLC 500™
processor communicate through the module's input and output image.
It lists the preliminary setup and operation required before the
module can function in a 1746 I/O system. Topics discussed include
how to:
• enter the module ID code
• select the Class 1 or Class 3 interface
• address your 1746-NI16 module
• select the proper input filter for each channel
• calculate the module update time
• interpret the module response to slot disabling
The module identification code is a unique number encoded for
each 1746 I/O module. The code defines for the processor the type
of I/O or specialty module residing in a specific slot in the 1746
chassis.
Catalog Number
1746-NI16I
1746-NI16V
Chapter
ID Code
Class 1 interface 3504
Class 3 interface 10403
Class 1 interface 3505
Class 3 interface 10406
Publication 1746-UM001A-US-P