NOTES:
1. No EOLR required.
2. 24 AWG min., 12 AWG max.
3. 80 Ohms max. per pair
between CC-5s.
Unshielded twisted pair
.5µF line to line
Shielded twisted pair
.3µF line to line
.4µF line to shield
4. Use twisted pair or twisted
shielded pair.
5. Terminate shields at one
end only.
6. Power limited to NFPA 70
per NEC 760.
7 . CC-5 terminals 9 - 14 are not
connected and can be used
to tie shields together.
NOTES:
1. No EOLR required.
2. 24 AWG min., 12 AWG max.
3. 80 Ohms max. per pair
between CC-5s.
Unshielded twisted pair
.5µF line to line
Shielded twisted pair
.3µF line to line
.4µF line to shield
4. Use twisted pair or twisted
shielded pair.
5. Terminate shields at one
end only.
6. Power limited to NFPA 70
per NEC 760.
7 . CC-5 terminals 9 - 14 are not
connected and can be used
to tie shields together.
Siemens Building Technologies
Fire Safety
PAIR A
SUPERVISED
POWER LIMITED
DO NOT USE
DO NOT USE
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
SEE NOTE 7
DO NOT USE
FIRST NIC-C
ONE SLOT OF CC-5
17
18
19
20
21
22
23
24
DO NOT USE
Figure 4
NIC-C Style 4 Network Wiring
PAIR B
SUPERVISED
POWER LIMITED
PAIR A
SUPERVISED
POWER LIMITED
DO NOT USE
DO NOT USE
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
SEE NOTE 7
DO NOT USE
FIRST NIC-C
ONE SLOT OF CC-5
17
18
19
20
21
22
23
24
DO NOT USE
Figure 5
NIC-C Style 7 Network Wiring
The screw terminals can accommodate one 12 -24 AWG or two 16-24 AWG.
DO NOT USE
1
2
3
4
5
6
7
9
10
11
12
13
14
15
SEE NOTE 7
DO NOT USE
ONE SLOT OF CC-5
17
18
19
20
21
22
23
DO NOT USE
1
2
3
4
5
6
7
9
10
11
12
13
14
15
SEE NOTE 7
DO NOT USE
ONE SLOT OF CC-5
17
18
19
20
21
22
23
DO NOT USE
5
DO NOT USE
8
1
2
3
4
5
6
16
9
10
11
12
13
14
SEE NOTE 7
LAST NIC-C
ONE SLOT OF CC-5
24
17
18
19
20
21
22
DO NOT USE
DO NOT USE
8
1
2
3
4
5
6
16
9
10
11
12
13
14
SEE NOTE 7
LAST NIC-C
ONE SLOT OF CC-5
24
17
18
19
20
21
22
DO NOT USE
P/N 315-033240-4
7
8
15
16
DO NOT USE
23
24
DO NOT USE
7
8
15
16
DO NOT USE
23
24