Connection And Setup Of A Dicn System (Option Kit Ekacpg); Cable For Remote Digital Controller (Option Kit Ekrupg) - Daikin EWYQ080DAYN Installation Manual

Packaged air-cooled water chillers
Hide thumbs Also See for EWYQ080DAYN:
Table of Contents

Advertisement

Double circuit unit
Connecting the pump (3~50 Hz, 400 V) in case of OPSC or
OPTC
-
For OPSC: pump contactor K1P is present
-
For OPTC: pump contactors K1P and K2P are present
For each pump connection, use a cable containing 3 conductors
+ ground with a minimum conductor section of 2.5 mm
The length of the earthing cable may not exceed
10 m. If the distance between pump and switch box is
more than 10 m, the pump must be earthed
independant of the switch box.
Maximum running current/pump as in the table below.
Units
EWYQ080+100
EWYQ130+150
EWYQ180~250
Connect L1, L2, and L3 to K1P (and to K2P in case of OPTC)
and the earthing wire to the earth terminal on the left side of K1P
as shown in the figures below.
Single circuit unit
1
Double circuit unit
Connection and setup of a DICN system
(option kit EKACPG)
(See
Annex
I,
"Installation examples for a DICN configuration" on
page
12)
For a system with chillers in a DICN configuration, the chillers have to
be connected as shown in the figure below.
1
2
Make the F1/F2 connection for DIII communication as shown on the
wiring diagram using a 2-core wire (0.75~1.25 mm
1000 m).
Pay attention to the polarity!
Installation manual
8
1
2
.
Maximum running current/pump
4.45 A
6.30 A
8.00 A
K1P
K1P
K1P
K2P
K2P
K2P
L1 L2 L3
L1
L1 L2
L2 L3
L3
L1
L1
L1
L2
L2
L2
L3
L3
L3
1
3
4
2
) (maximum of
DICN setup settings on the digital controller
When a DICN system is installed, adjust the settings on the digital
controller as shown in the tables below:
Service menu, submenu, communication
COMMUNICATION PCB (fifth screen)
Unit 1
Master
DIII:
YES
ADDR:
1-00
POWER:
Y
Service menu, submenu, DICN
DICN SETTINGS (first screen)
Unit 1
Master
(*)
MS OPTION:
Y
UNIT:
MASTER SLAVE
NR OF SLAVES:
3
(*) The master unit must be set as last in row, otherwise set to N and back to Y.
DICN SETTINGS (second screen)
Unit 1
Master
ADD SL1:
1-01
ADD SL1:
1-02
ADD SL1:
1-03
NOTE
When the user enters the service menu, the DIII
communication stops.
When the user leaves the service menu, the DIII
communication restarts.
It takes 10 minutes before DIII communication is
fully re-established.
If communication fails after 10 minutes, the
network
safety
COMM.PROBLEM"
symptom 12 in the chapter "Troubleshooting" in
the operation manual).

Cable for remote digital controller (option kit EKRUPG)

In case you prefer to operate the unit from a distance, a remote digital
controller can be connected to the PCB inside the unit. Specifications
2
of the cable: 0.75 mm
4 wire, and maximum 500 m long.
Setting the addresses on the remote digital controller
When a remote digital controller is used, the address has to be set by
means of DIP-switches according to the drawing below:
Main (A4P)
remote controller
SUB
S1A
MAIN
TERM
S2A
ON
■ = DIP-switch position
Also refer to the wiring diagram delivered with the unit.
Unit 2
Unit 3
Unit 4
Slave 1
Slave 2
Slave 3
YES
YES
YES
1-01
1-02
1-03
N
N
N
Unit 2
Unit 3
Unit 4
Slave 1
Slave 2
Slave 3
Y
Y
Y
SLAVE
SLAVE
Unit 2
Unit 3
Unit 4
Slave 1
Slave 2
Slave 3
error
message
"OU4:PCB
appears
(also
Sub (A5P)
remote controller
SUB
S1A
MAIN
TERM
S2A
OFF
ON
OFF
EWYQ080~250DAYN
Packaged air-cooled water chillers