Daikin F-Series Service Manual page 231

Inverter multi for 2 rooms
Hide thumbs Also See for F-Series:
Table of Contents

Advertisement

Troubleshooting
Troubleshooting
Check No.08
Refer to P.242
Check No.13
Refer to P.244
220
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check the power supply
Check No.
08
Discharge pressure check.
Judgement
Normal
Check No.
13
Check for short-circuit.
Normal
YES
Check the electrolytic capacitor
voltage.
DC270±30V?
YES
Electricals
or compressor harnesses
connected as
specified?
Turn off the power. Disconnect the
harnesses U, V and W.
Check with the inverter checker (∗).
Any LED off?
NO
Abnormal
NO
NO
NO
YES
SiBE12-712
Replace the stop valve.
Replace the outdoor unit
PCB, outdoor unit fan.
Replace the four way valve
coil.
Replace the outdoor unit
PCB.
Reconnect as specified.
∗ Inverter checker
Part No.: 1225477
Correct the power supply or
replace the outdoor unit
PCB.
Replace the compressor.
(R7047)
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents