Download Print this page

Haier AP48KS1ERA Operation And Installation Manual page 20

Cabinet type
Hide thumbs Also See for AP48KS1ERA:

Advertisement

Installation Procedure
Note:
Electrical wiring must be done by qualified person.
The power supply connects from the outdoor unit.
The connecting cable and power cable are self-provided.
Use copper wire only.
Air conditioner must use an exclusive line (over 30A)
When installing air conditioner in a wet place, try to use a circuit breaker against current leakage.
When installing in other places, use circuit breaker as far as possible.
The breaker of the air conditioner should be all-pole switch; and the distance between its two contacts should be no less
than 3 mm.
Such means for disconnection must be incorporation in the fixed wiring
The parameter of connecting cable is H05RN-F 4G 2.5mm
The parameter of the power cable should be over H07RN-F 5G 4.0mm
Wiring of indoor unit
Insert the cable from outside the wall hole where piping already exist.
Pull it out from front.
Loosen terminal screws and insert cable end fully into terminal block,
then tighten it.
Pull the cable gently to make sure it is tight.
Replace cover after wiring.
Wiring of outdoor unit
Insert the cable from inside the wall hole where piping already exists.
Pull it out from front.
Loose terminal screw and insert cable end fully into terminal block,
then tighten it.
Pull the cable gently to make sure it is tight.
Replace cover after wiring.
Note:
When connecting indoor and outdoor wire, check the number on indoor and outdoor terminal blocks. Incorrect wiring may
damage air conditioner's controller or cause operation failure.
.
2
2
18
Electrical wiring
OK
NO
terminal block
table clamp

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Ap48ds1eraAp60ks1era