3) Precautions in bending
If it is necessary to bend or stretch the tubing,
use the spring which is attached to the tubing in
stead of pipe bender.
• Please make a careful notice to make a smooth
line.
• Hold the tubing with your two hands closely and
then bend or stretch it slowly not to make any
crack.
• Remember that the radius (R) should not exceed
70mm (Refer to Fig. 1)
Do not repeat the bending process to prevent the
tubing from cracking or crushing.
Keep in mind that the bending part should not be
cracked and make the radius (R) as long as possible
(Refer to Fig. 2)`
5-4. Connecting Piping to Outdoor Unit
1) Connecting pipings to the outdoor unit
Upon connecting 4-way valves, please weld connecting pipes using elbows instead of connecting pipes with
flare nuts.

5-5. Connecting the Cable

Open the control board cover from the outdoor unit by
removing the screws.
Connect wires to the terminals on the control board
individually and secure the cables onto the control
board with clamp.
Spring
(Fig. 1)
(Fig. 2)
Installation
R70mm
Service Manual 27