LG MLP-F8081CL Service Manual page 30

Floor standing type air conditioner
Table of Contents

Advertisement

Installation
Set the both 3-way(liquid side) and 3-way(gas side) valves to open position with the Hexagonal
wrench for the unit operation.
Checking a gas leakage for the left piping
• Connect the manifold gauge to the service port of 3-way(gas side) valve.
Measure the pressure.
• Keep it for 5 - 10 minutes.
Ensure if the pressure indicated on the gauge is as same as that of measured at first time.
Indoor unit
CLOSE
30 Floor Standing Type Air Conditioner
Liquid side
Closed
Gas side
Closed
CLOSE
Outdoor unit