3. Auto Operation (Cooling Model only)
The operation procedure is as following.
Auto Operation for Cooling
Operation Condition
When Switch to
Auto Operation
Intake Air Temp.
Setting Temp. +1°C
(Compressor ON)
Setting Temp. -1°C
(Compressor OFF)
Indoor Fan Speed
Compressor
Press Start/Stop Button
Select Auto Operation Mode
Check the Room temperature
Intake-air Temperature
Over 26°C
Over 24°C~below 25.5°C
Over 22°C~below 23.5°C
below 21.5°C
ON
Setting temperature
25°C
Intake air -1.0°C
Intake air -0.5°C
Intake air Temperature(18°C, MAX)
3 minutes
Fuzzy Speed
OFF
Operation Details
Fan speed
3 minutes
ON
OFF
Service Manual 17