Siemens RDG400 Basic Documentation page 32

Room thermostat with display, for vav
Hide thumbs Also See for RDG400:
Table of Contents

Advertisement

Name
Diagnostics and test
d01
Application type
d02
X1 status
d03
X2 status
d04
D1 status
d05
Test mode for checking
actuator direction Y1/Y2
(press left button to escape)
32 / 42
Siemens
Building Technologies
Factory setting
Diagnostics
Diagnostics
Diagnostics
Diagnostics
---
RDG400 Basic Documentation
Functions
Range
0 = (no application)
1 = 2-pipe
2 = 2-pipe with electrical heater
3 = 2-pipe with radiator
4 = 4-pipe
5 = 2 stage heating or cooling
6 = 4-pipe with electrical heater
0 = not activated (for DI)
1 = activated (DI)
0...49 °C = cur temp value (for AI)
00
= H/C input closed
100
= H/C input open
0 = not activated (for DI)
1 = activated (DI)
0...49 °C = cur temp value (for AI)
00
= H/C input closed
100
= H/C input open
0 = not activated (for DI)
1 = activated (DI)
00
= H/C input closed
100
= H/C input open
"---" = no signal at outputs Y1 and Y2
OPE = output Y1 forced opening
CLO = output Y2 forced closing
CE1P3182en
19 Jun 2009