Set Ao Value - DAE INSTRUMENT CC1000a06 Reference

Smart lighting control system modbus gateway
Table of Contents

Advertisement

Set AO Value

✦ CC1000 Address 1
✦ LT address 19, AO 1
➡ Register Address = (19 + 127) x 4 + (1 - 1) = 584
➡ RH = 584 div 256 = 2
➡ RL = 584 mod 256 = 72
✦ AO Value = 50%
➡ DL = 50% / 1% = 50
✴ Note that the allowed values for AO is from 0 to 100%.
Query
Register Address
Register Address
CC1000
CC1000
Function
Function
Address
Address
Code
Code
high (RH)
1
16
Reply
CC1000
CC1000
Function
Function
Address
Address
Code
Code
1
16
CC1000 Modbus Reference 2.10e!
Number of Registers
Number of Registers
low (RL)
high
2
72
0
Register Address
Register Address
high (RH)
low (RL)
2
72
Write Data
Write Data
Byte
Byte
Count
Count
low
high (DH)
1
2
0
Number of Registers
Number of Registers
high
low
0
1
CRC
CRC
low (DL)
low
high
50
11
205
CRC
CRC
low
high
128
103
41/122

Advertisement

Table of Contents
loading