Set Group On/Off; Activate Pattern; Set Do On/Off - DAE INSTRUMENT CC1000a06 Reference

Smart lighting control system modbus gateway
Table of Contents

Advertisement

Set Group On/Off

Data Format
Set Group To
Value
On
255
Off
0
Command Format
Query and Reply
CC1000
5
Address
Group to Register Address Conversion
❖ Reg = Group

Activate Pattern

Data Format
✦ Patterns can only be activated, the activation code is 255, there is no off for a pattern.
Command Format
Query and Reply
CC1000
5
Address
Pattern to Register Address Conversion
❖ Reg = Pattern + 63

Set DO On/Off

Data Format
Set DO To
Value
On
255
Off
0
Command Format
Query and Reply
CC1000
5
Address
LT to Register Address Conversion
❖ Reg = (LT + 31) x 8 + (DO - 1)
CC1000 Modbus Reference 2.10e!
Reg-H
Reg-L
Reg-H
Reg-L
Reg-H
Reg-L
Group
0
On/Off
255
0
DO On/Off
0
CRC-L
CRC-H
CRC-L
CRC-H
CRC-L
CRC-H