Single Do Pulse Out; Dual Do Pulse Out - DAE INSTRUMENT CC1000a06 Reference

Smart lighting control system modbus gateway
Table of Contents

Advertisement

Single DO Pulse Out

✦ CC1000 Address 1
✦ Send out pulse from LT 15, DO 6
➡ Register Address = (15 + 95) x 8 + (6 - 1) = 885
➡ RH = 885 div 256 = 3
➡ RL = 885 mod 256 = 117
➡ Pulse Out
➡ DH = 255
Query and Reply
CC1000
CC1000
Function
Function
Address
Address
Code
Code
1
5

Dual DO Pulse Out

✦ CC1000 Address 1
✦ Send out a pulse from both DO 7 and 8 simultaneously on LT 64
➡ Register Address = (64 + 319) x 4 + (7 - 1) div 2 = 1535
➡ RH = 1535 div 256 = 5
➡ RL = 1535 mod 256 = 255
➡ Pulse Out
➡ DH = 255
Query and Reply
CC1000
CC1000
Function
Function
Address
Address
Code
Code
1
5
CC1000 Modbus Reference 2.10e!
Starting Register
Starting Register
high (RH)
low (RL)
3
117
Starting Register
Starting Register
high (RH)
low (RL)
5
255
Force Data
Force Data
high (DH)
low
255
0
Force Data
Force Data
high (DH)
low
255
0
CRC
CRC
low
high
157
164
CRC
CRC
low
high
188
198
38/122