Refrigerant Piping System - Mitsubishi Electric PQHY-P-T(S)LMU-A Installation Manual

Air-conditioners for building application
Table of Contents

Advertisement

Caution:
Use a vacuum pump with a reverse flow check valve.
- If the vacuum pump does not have a reverse flow check valve, the vacuum
pump oil may flow back into the refrigerant cycle and cause deterioration of
the refrigerant oil.
Do not use the tools shown below used with conventional refrigerant.
(Gauge manifold, charge hose, gas leak detector, check valve,
refrigerant charge base, vacuum gauge, refrigerant recovery
equipment)
- Mixing of conventional refrigerant and refrigerant oil may cause the
refrigerant oil to deteriorate.
- Mixing of water will cause the refrigerant oil to deteriorate.
- R410A refrigerant does not contain any chlorine. Therefore, gas leak
detectors for conventional refrigerants will not react to it.
Manage tools used for R410A carefully.
- If dust, dirt, or water gets in the refrigerant cycle, the refrigerant oil will
deteriorate.
Never use existing refrigerant piping.
- The large amount of chlorine in conventional refrigerant and refrigerant oil
in existing piping will cause the new refrigerant to deteriorate.
Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing.
- If dust, dirt, or water get into the refrigerant cycle, the oil will deteriorate
and the compressor may fail.
Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.
Do not use special detergents to wash the piping.

9.2. Refrigerant piping system

Example of refrigerant piping system
[Fig. 9.2.1] (P.4, P.6 - 7)
Heat source model
Gas side
Liquid pipe
Model number
The first branch of P144 ~ P240
Joint
4-Branch header (Downstream indoor unit model total <= 72)
8-Branch header (Downstream indoor unit model total <= 144)
10-Branch header (Downstream indoor unit model total <= 240)
Heat source twinning kit
A Heat source unit
C Indoor unit
E Heat source twinning kit
*1 ø12.7 for over 90 m [295-1/4in]
*2 ø12.7 for over 40 m [131-3/16in]
*3 The pipe sizes listed in columns A1 to A3 in this table correspond to the sizes
for the models listed in the unit 1, 2, and 3 columns. When the order of the
models for unit 1, 2, and 3 change, make sure to use the appropriate pipe size.
*4 B If the piping length after the first joint exceeds 40 m (≤ 90 m), use the one
size larger liquid pipe for the indoor unit. (for PQHY-P·T(S)LMU-A/Y(S)LMU-A)
*5 C When the height difference between the indoor units is 15 m or greater
(≤ 30 m), use the one size larger liquid pipe for the indoor unit (lower side). (for
PQHY-P·T(S)LMU-A/Y(S)LMU-A)
[Fig. 9.2.2] (P.5 - 7)
Heat source model
Low-pressure side
Liquid pipe
Model number
Heat source twinning kit
Low-pressure gas pipe
A Heat source unit
C BC controller (main)
E Indoor unit (06 ~ 54)
G Heat source twinning kit
*1 The pipe sizes listed in columns A1 to A2 in this table correspond to the sizes
for the models listed in the unit 1 and 2 columns. When the order of unit 1 and
2 is changed, make sure to use the appropriate pipe size for the model.
Precautions for heat source unit combinations
Refer to [Fig. 9.2.3] for the positioning of twinning pipes.
[Fig. 9.2.3] (P.8)
<A> When the piping (from the twinning pipe) exceeds 2 m [6 ft], include a trap
(gas pipe only) within 2 m [6 ft]. Make sure the height of the trap is 200 mm
[7-7/8 in] or more.
If there is no trap, oil can accumulate inside the pipe, causing a shortage of
oil damaging the compressor. (for PQHY-P·TSLMU-A/YSLMU-A)
<B> Example of piping connection (for PQHY-P·TSLMU-A/YSLMU-A)
Indoor unit
A
Within 2 m [6 ft]
C
Field-supplied piping
E
Straight pipe length that is 500 mm [19-11/16 in] or more
G
26
Liquid side
Total capacity of indoor units
Gas pipe
Downstream unit model total
The first branch of P264 ~ P360
B 1st branch
D Cap
F Header
High-pressure side
Total capacity of indoor units
Gas pipe
Downstream unit model total
High-pressure gas pipe
B BC controller (standard)
D BC controller (sub)
F Indoor unit (72 ~ 96)
Trap (gas pipe only)
B
Twinning pipe
D
Twinning kit
F
Precautions for heat source unit combinations
Refer to [Fig. 9.2.4] for the positioning of twinning pipes.
[Fig. 9.2.4] (P.8 - 9)
<A> Install the piping so that oil will not accumulate in the stopped heat source
unit. (both the liquid and the gas side for PQHY-P·TSLMU-A/YSLMU-A, the
high-pressure side only for PQRY-P·TSLMU-A/YSLMU-A)
1.
The NG example shows that oil accumulates because the units are installed
on a reverse gradient while unit 1 is in operation, and unit 3 is stopped.
2.
The NG example shows that oil accumulates into units 1 and 2 while unit 3
is in operation, and units 1 and 2 are stopped. Vertical pipe height (h) should
be 0.2 m (7-7/8 in) or below.
3.
The NG example shows that oil accumulates into unit 1 while unit 3 is in
operation, and unit 1 is stopped. Vertical pipe height (h) should be 0.2 m
(7-7/8 in) or below.
4.
The NG example shows that oil accumulates into unit 3 while unit 1 is in
operation, and unit 3 is stopped. Vertical pipe height (h) should be 0.2 m
(7-7/8 in) or below.
<B> Slope of twinning pipes (for PQHY-P·TSLMU-A/YSLMU-A)
Make sure the slope of the twinning pipes are at an angle within ±15° to the
horizontal plane.
If the slope exceeds the angle specified, the unit may be damaged.
<C> Example of piping connection (for PQRY-P·TSLMU-A/YSLMU-A)
Slope downward
A
BC controller (standard or main)
C
Slope of the twinning pipe is at an angle within ±15° to the ground
E
Twinning pipe (low-pressure side)
F
Field-supplied piping (low-pressure connecting pipe: between heat source
H
units)
Field-supplied piping (low-pressure main pipe: to BC controller)
I
Field-supplied piping (high-pressure main pipe: to BC controller)
J
Caution:
Do not install traps to prevent oil backflow and compressor start-up
failure.
Do not install solenoid valves to prevent oil backflow and compressor
start-up failure.
Do not install a sight glass because it may show improper refrigerant
flow.
If a sight glass is installed, inexperienced technicians that use the
glass may overcharge the refrigerant.
Slope upward
B
Twinning pipe
D
Twinning pipe (high-pressure side)
G

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Pqry-p-t(s)lmu-aPqhy-p-y(s)lmu-aPqry-p-y(s)lmu-a

Table of Contents