SLP-15AAUW SLP-15AAUW Remarks * PLFY-P-NCMU-E should used together with SLP-15AAUW. * Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual. * Due to continuing improvement, above specification may be subject to change without notice.
Page 6
1. SPECIFICATIONS Model PLFY-EP08NEMU-E PLFY-EP12NEMU-E PLFY-EP15NEMU-E PLFY-EP18NEMU-E Power source 1-phase 208-230 V 60Hz Cooling capacity *1 BTU/h 8,000 12,000 15,000 18,000 *1 kW Power input 0.03 0.03 0.03 0.03 Current input 0.31 0.31 0.31 0.34 Heating capacity *2 BTU/h 9,000 13,500 17,000 20,000...
Page 7
1. SPECIFICATIONS Model PLFY-EP24NEMU-E PLFY-EP30NEMU-E PLFY-EP36NEMU-E PLFY-EP48NEMU-E Power source 1-phase 208-230 V 60Hz Cooling capacity *1 BTU/h 24,000 30,000 36,000 48,000 *1 kW 10.6 14.1 Power input 0.04 0.04 0.07 0.11 Current input 0.43 0.45 0.73 1.01 Heating capacity *2 BTU/h 27,000 34,000 40,000...
Page 8
1. SPECIFICATIONS Model PLFY-P08NEMU-E PLFY-P12NEMU-E PLFY-P15NEMU-E PLFY-P18NEMU-E Power source 1-phase 208-230 V 60Hz Cooling capacity *1 BTU/h 8,000 12,000 15,000 18,000 *1 kW Power input 0.02 0.02 0.02 0.02 Current input 0.25 0.26 0.29 0.29 Heating capacity *2 BTU/h 9,000 13,500 17,000 20,000...
Page 9
1. SPECIFICATIONS Model PLFY-P24NEMU-E PLFY-P30NEMU-E PLFY-P36NEMU-E PLFY-P48NEMU-E Power source 1-phase 208-230 V 60Hz Cooling capacity *1 BTU/h 24,000 30,000 36,000 48,000 *1 kW 10.6 14.1 Power input 0.04 0.05 0.08 0.10 Current input 0.41 0.56 0.90 0.99 Heating capacity *2 BTU/h 27,000 34,000 40,000...
4. ELECTRICAL WIRING DIAGRAMS PLFY-EP08, 12, 15, 18, 24, 30, 36, 48NEMU-E LED2 LED1 * Be sure to turn off the source power and then disconnect fan motor connector. TH22 (Failure to do so will cause trouble in Fan motor) tº...
Page 16
4. ELECTRICAL WIRING DIAGRAMS PLFY-P08, 12, 15, 18, 24, 30, 36, 48NEMU-E LED2 LED1 * Be sure to turn off the source power and then disconnect fan motor connector. TH22 (Failure to do so will cause trouble in Fan motor) tº...
8. OPTIONAL PARTS 8-1. Optional parts line up for the Indoor unit 8. OPTIONAL PARTS Air outlet shutter plate Multi-function casement High efficiency filter element PLFY-EP-NEMU-E PAC-SJ37SP-E PAC-SJ41TM-E PAC-SH59KF-E Wireless signal receiver Flange for fresh air intake PLFY-EP-NEMU-E PAR-SR3LA-E PAC-SH65OF-E External heater adapter PLFY-P-NEMU-E PAC-YU25HT...
8. OPTIONAL PARTS 8-3. High efficiency filter element Life span: 2,500 hr (Dust concentration 0.15mg/m ); Colorimetric method 65% (JIS 11 class); No re-production. * The actual dust situation affects the filter life span, which should be considered at the applying site. Material: Electrostatic polyolefin fiber High efficiency filter element PAC-SH59KF-E should be used together with the Multi-function casement PAC-SJ41TM-E.
8. OPTIONAL PARTS 8-5. Wireless signal receiver Using the wireless signal receiver to use wireles remote controller. The corner panel(the other side of refrigerant piping) is changed for the wireless signal receiver. Item Wireless signal receiver Quantity Signal receiver Shape Detailed installation information should be referred to its Installation Manual.
8. OPTIONAL PARTS 8-7. External heater adapter External heater adapter PAC-YU25HT is a set of special wiring parts for controlling the electric heater* with the air conditioner system. *The electric heater should be designed and prepared at the site. A basic connection method is shown as follows:(For details, refer to its Installation Manual.) (1) Basic wiring Indoor unit Outdoor unit...
Page 32
ELECTRICAL CHARACTERISTICS Electrical characteristics I.ELECTRICAL CHARACTERISTICS 1. Power supply for Indoor unit ..........................32 1-1. Electrical characteristics of Indoor unit ....................32 MEE16K008_U...
Page 33
1. Power supply for Indoor unit 1-1. Electrical characteristics of Indoor unit I.ELECTRICAL CHARACTERISTICS 1. Power supply for Indoor unit Symbols: MCA: Minimum Circuit Ampacity (=1.25xFLA) FLA: Full Load Amps IFM: Indoor Fan Motor Output: Fan motor rated output Indoor Unit Model Volts Voltage range...
Page 34
- Doing so may cause the unit or pipes to burst, or result in explosion or fire during use, during repair, or at the time of disposal of the unit. - It may also be in violation of applicable laws. - MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong type of refrigerant. ■...