Mhb44Ind 4 Channels Pulse Input And 4 Channel Analogue Output Module; Mao04Ind 4 Channel Analogue Output Module; System Identification; Sc300E Rtts 8.30-005 - ABB Triguard SC300E Safety Manual

Triple modular redundant safety controller
Hide thumbs Also See for Triguard SC300E:
Table of Contents

Advertisement

11.2 MHB44IND 4 channels pulse input and 4 channel analogue output module.

The Piano module may only be used with TriBuild for Windows version 1.42 and RTTS 8.3-006
or above with the following restrictions.
1. The registers used for the analogue outputs must be initialised to 256 or greater to prevent
the module losing health.
2. The ladders for the analogue outputs must be configured to prevent the output registers
going below 256 resulting in the module losing health.

11.3 MAO04IND 4 channel analogue output module.

The following conditions must be applied when using the analogue output module
1. The registers used for the analogue outputs must be initialised to 256 or greater to prevent
the module losing health.
2. The ladders for the analogue outputs must be configured to prevent the output registers
going below 256 resulting in the module losing health.

11.4 System identification

Both RTTS 8.30 versions are identified by the title in the history report and by the
check sums of the EPROM's as follows:

11.4.1 SC300E RTTS 8.30-005

Version 8.30 LOC SC-300E ROM System-005 Generated 19-May-2000 11:07
U86
U106 -
U87
U107 -

11.4.2 SC300E RTTS 8.30-006

Version 8.30 LOC SC-300E ROM System-006 Generated 12-Jul-2000 15:38
U86
U106 -
U87
U107 -
Issue 5 - September 2006
-
486Eh
0BC0h
-
46ACh
3E43h
-
4885h
0BCFh
-
469Fh
3D53h
Page 56 of 65