Clearing Fault History
The fault buffer can be cleared with the pushbutton while
the Fault History Display (FL) menu is active by holding
down the pushbutton for 5 seconds or more. For indication
that the fault buffer is clear the IFC will flash segments A
and D of the right-most seven segment displays one sec-
ond on and one second off three times after the fault clear
command has been recognized.
48
EXTENDED DISPLAY MODE – DISPLAY PROPERTIES
Extended Display Mode
If the pushbutton is pressed during the power-up se-
quence, IFC will turn on the extended display mode. The
extended display mode modifies the display operation per
the following table: