Download Print this page

Toshiba VF-P7 Instruction Manual page 5

Compliance with ce marking and ul standard 200v class 400v class
Hide thumbs Also See for VF-P7:

Advertisement

     
1.3. Compliance with EMC directive
(1) Recommended EMI noise filters(refer to Table 2) should be installed to the input. These
can reduce the conducted and radiated noise.
《3-phase 200V class》
Type form
VFP7-2185P
VFP7-2220P
VFP7-2300P
VFP7-2370P
VFP7-2450P
VFP7-2550P
VFP7-2750P
VFP7-2900P
VFP7-2110KP
Note)
FN258,3258
FN359
FN3359
(2) The main cables such as input to the EMI filter and output of the inverter and the signal
cables should be shielded, then cable length should be wired as short as possible. The main
input cable should be separated from the main output cable, and cables for control signal
also should be separated from main cables, not wiring parallel and not bundling, cross the
wires where necessary.
(3) Install EMI filter and inverter on the same metal back plate in an inverter panel. The metal
back plate or the cubicle must be grounded absolutely, by using short thick wires, separated
from the main cables.
(4) Please separate input cable to EMI filter from output cable as much as possible.
(5) Shielded cables should be grounded on the metal back plate in order to reduce the radiated
noise from the other cables. It is an effective measure that shielded cables are grounded
close to the inverter or/and operation panel or/and EMI filter(less than 10cm).
(6) Installation of the zero-phase and/or the ferrite core can also effectively reduce the radiated
noise further.(Input or/and output of inverter)
Table 2. Recommended EMI filter selection
Filter type
FN258-100/35 or
FN3258-100/35
FN258-100/35 or
FN3258-100/35
FN258-130/35 or
FN3258-130/35
FN258-180/07 or
FN3258-180/40
FN258-130/35×2P or
FN258-250/07 or
FN3359-250/28
FN258-130/35×2P or
FN258-250/07 or
FN3359-250/28
FN359-300/99 or
FN3359-320/99
FN359-400/99 or
FN3359-400/99
FN359-500/99
FN3359-500/99
480V or less
400V or less,    FN359H
500V or less,
         E6580971③
《3-phase 400V class》
Type form
VFP7-4185P
VFP7-4220P
VFP7-4300P
VFP7-4370P
VFP7-4450P
VFP7-4550P
VFP7-4750P
VFP7-4900P
VFP7-4110KP
VFP7-4132KP
VFP7-4160KP
VFP7-4200KP
VFP7-4220KP
VFP7-4280KP
VFP7-4315KP
520V or less
FN3359HV
- 4 -
Filter type (NOTE)
FN258-42/07 or
FN3258-42/47
FN258-55/07 or
FN3258-55/52
FN258-75/34 or
FN3258-75/32
FN3258-75/52 or
FS5992-72/52
FN258-100/35 or
FN3258-100/35
FN3258-130/35 or
FS5992-130/35
FN258-180/07 or
FN3258-180/40
FN3359(HV)-250/28
FN359(H)-250/99 or
FN3359(HV)-250/28
FN359(H)-300/99 or
FN3359(HV)-320/99
FN359(H)-400/99 or
FN3359(HV)-400/99
FN359(H)-500/99 or
FN3359(HV)-500/99
FN359(H)-500/99 or
FN3359(HV)-500/99
FN359(H)-600/99 or
FN3359(HV)-600/99
FN359(H)-900/99 or
FN3359(HV)-1000/99
690V or less

Advertisement

loading