14.1 Read the module's firmware version
Command
$IDF(CHK)(cr)
$
ID
F
Syntax
CHK
description
(cr)
Response
!IDMODMMYY(CHK)(cr)
?ID(CHK)(cr)
EX: Send command:$01F...Read the TRP-C28's version.
Response:"!01C280605"....... The TRP-C28's version date is "06/2005".
14.2 Read the module reset status
Command
Syntax
description
Response
EX: Send command:$015...Read the TRP-C28's reset state .
Response:"!011"....... The TRP-C28 has been reset.
*If the module is system halt or detect abnormal voltage , the module will restart and reset the flag to "1" .
$ID5(CHK)(cr)
$
ID
5
CHK
(cr)
!IDS(CHK)(cr)
?ID(CHK)(cr)
First leading code
Address of setting module 00-FF(HEX)
Command for reading module's version
Checksum
Carriage return
MOD :The module type
MM:Release Month
YY : Release Year
Command Invalid
First leading code
Address of setting module 00-FF(HEX)
Command for reading reset status
Checksum
Carriage return
S =1 has been reset
S=0 not been reset
Command Invalid