Troubleshooting (cont'd)
5. When there is no warm air in the current mode
5. When there is no warm air in the current mode
1) Checklist :
(1) Is the set temperature of the remote control lower than room temperature in the Heat mode?
(2) Is the Indoor PCB properly connected with the CN71 connector?
2) Troubleshooting procedure
After training on, the Heating starts
Is #9 of Micom (IC04) DC 5.0 V?
Is the number checking #12 of IC06 (ULN2003A) LOW?
Is voltage rating between CN71 #3 and
4 way valve of the outdoor unit or connection
Replace 4 way valve check connection cable
20
in five minutes.
NO
YES
YES
CN71 #5 within ±10% range?
YES
cable is abnormal.
YES
Normal
NO
Micom is abnormal.
NO
IC 06 is abnormal.
NO
RY 73 is abnormal.
Replace PCB