Hysteresis: Behavior Of Heating And Cooling - Siemens RDG400KN Basic Documentation

Room thermostats with knx communications
Hide thumbs Also See for RDG400KN:
Table of Contents

Advertisement

34 / 87
Siemens
Building Technologies
Single-duct and
--
radiator
Single-duct and
Water sequence
heating/cooling
coil
3.6.2

Hysteresis: Behavior of heating and cooling

∂ The control sequences heating and cooling depend on the heating and cooling
setpoints and the room temperature
∂ The thermostat remains in the heating sequence as long as the room
temperature does not reach the cooling setpoint
∂ The thermostat remains in the cooling sequence as long as the room
temperature does not reach the heating setpoint
The value of the output and the sequence as a function of the room temperature is
shown in the following diagram in the case of a heating and cooling system:
1 = Heat
0 = Cool
100%
0
Wheat
RDG400KN,RGD405KN Basic documentation
Wheat = current setpoint heating
TR
Wcool = current setpoint cooling
Wcool
CE1P3192en
2017-02-17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rgd405kn

Table of Contents