Download Print this page

Lists Of Parameters - YOKOGAWA UM350 User Manual

Digital indicator with alarms
Hide thumbs Also See for UM350:

Advertisement

2. Lists of Parameters

* Parameters relating to PV should all be set in real numbers.
For example, use temperature values to define alarm setpoints for
temperature input.
Operating Parameters
Parameter
Name of Parameter
Setting Range and Description
Initial Value
Symbol
Alarm 1-setpoint
PV alarm: -100.0 to 100.0% of PV input range
PV high limit
alarm:
(A1)
100.0% of
Alarm 2-setpoint
PV input range
PV low limit
(A2)
alarm:
Alarm 3-setpoint
0.0% of
PV input range
(A3)
Alarm 4-setpoint
(A4)
PV peak value
Displays the maximum value of PV input during operation.
This parameter is not to be set.
(PEAK)
PV bottom value
Displays the minimum value of PV input during operation.
This parameter is not to be set.
(BOTM)
PV input filter
OFF, 1 to 120 second
OFF
Used when the PV input fluctuates.
(FL)
PV input bias
-100.0% to 100.0% of PV input range span
0.0% of PV
Used to correct the PV input value.
input range
(BS)
span
Setup Parameters
Alarm/Communication-related Parameters
Parameter
Name of Parameter
Setting Range and Description
Initial Value
Symbol
Alarm-1 type
OFF
1
1: PV high limit (energized, no stand-by action)
(AL1)
2: PV low limit (energized, no stand-by action)
9: PV high limit (de-energized, no stand-by action)
Alarm-2 type
2
10: PV low limit (de-energized, no stand-by action)
11: PV high limit (energized, stand-by action)
(AL2)
12: PV low limit (energized, stand-by action)
Alarm-3 type
1
19: PV high limit (de-energized, stand-by action)
20: PV low limit (de-energized, stand-by action)
(AL3)
21: Fault diagnosis output
Alarm-4 type
2
Turns on in case of input burnout, A/D
converter failure, or reference junction
(AL4)
compensation (RJC) failure.
22: FAIL output
Turns off in case of program failure, ROM
failure, RAM failure, or power failure. This
output is on during normal operation. If it
turns off, the retransmission output is set to
0%, the alarm output is set to OFF, and the
indicator stops.
See "List of Alarm Types" on the right side of this
manual for details on how these Alarm Type
parameters behave.
Alarm-1 hysteresis
0.0 to 100.0% of PV input range span
0.5% of PV
input range span
(HY1)
Hysteresis can be set in the alarm setpoint.
Setting hysteresis prevents relays from
Alarm-2 hysteresis
chattering.
(HY2)
Hysteresis setting for PV high limit alarm
Alarm-3 hysteresis
Point of on-off action
Output
(Alarm setpoint)
(HY3)
Alarm-4 hysteresis
On
(HY4)
Hysteresis
Off
PV value
Alarm-1 delay timer
An alarm is output when the delay timer expires
0.00
after the alarm setpoint is reached.
(DY1)
0.00 to 99.59 (min, sec.) (enabled when alarm-
1 type "AL1" is 1, 2, 9, 10, 11, 12, 19, and 20)
PV
Alarm setpoint
Hysteresis
Delay timer
Delay timer
Alarm output
off
on
Time
Alarm-2 delay timer
0.00 to 99.59 (min, sec.) (enabled when alarm-
2 type "AL2" is 1, 2, 9, 10, 11, 12, 19, and 20)
(DY2)
Alarm-3 delay timer
0.00 to 99.59 (min, sec.) (enabled when alarm-
3 type "AL3" is 1, 2, 9, 10, 11, 12, 19, and 20)
(DY3)
Alarm-4 delay timer
0.00 to 99.59 (min, sec.) (enabled when alarm-
4 type "AL4" is 1, 2, 9, 10, 11, 12, 19, and 20)
(DY4)
Protocol selection
0: PC link communication
0
1: PC link communication (with checksum)
2: Ladder communication
(P.SL)
7: MODBUS (ASCII)
8: MODBUS (RTU)
Baud rate
0: 600, 1: 1200, 2: 2400, 3: 4800, 4: 9600 (bps)
4
(BPS)
Parity
0: None
1
1: Even
(PRI)
2: Odd
Stop bit
1, 2
1
(STP)
Data length
7, 8
8
Fixed at 7, when the P.SL parameter is set to
(DLN)
MODBUS (ASCII).
Fixed at 8, when the P.SL parameter is set to
MODBUS (RTU) or Ladder Communication.
Address
1 to 99
1
However, the maximum number of stations
(ADR)
connectable is 31.
Minimum response
0 to 10 (
10 ms)
0
time
(RP.T)
If this parameter symbol appears, press the SET/ENT key to return to the FUNC menu.
(TEST)
Caution: Do not change the setpoint of the TEST parameter, otherwise the indicator will be disabled.
* The "User Setting" column in the table below is provided for the customer to record setpoints.
Input-/Output-related Parameters
Parameter
Name of Parameter
Setting Range and Description
Symbol
User setting
PV input type (PV INPUT
OFF, 1 to 18, 30, 31, 35 to 37, 40, 41, 50, 51, 55, 56
terminals)
See Instrument Input Range Codes in
Initial
(IN)
11
-
12
-
13
terminals
Settings User's Manual
.
°C: degree Celsius
PV input unit
°F: Fahrenheit
(UNIT)
Max. value of PV input
Set the PV input range, however RL < RH
range
-Temperature input
(RH)
Set the range of temperature that is actually indicated.
- Voltage input
Set the range of a voltage signal that is applied.
Min. value of PV input
The scale across which the voltage signal is actually
range
indicated should be set using the parameters
(RL)
Maximum Value of PV Input Scale (SH) and Minimum
Value of PV Input Scale (SL).
PV input decimal point
0 to 3
position (displayed
Set the position of the decimal point of voltage-
(SDP)
at voltage input)
mode PV input.
0: No decimal place
1: One decimal place
2, 3: Two, three decimal places
Max. value of PV input
-1999 to 9999, however SL < SH
scale
Set the read-out scale of voltage-mode PV input.
(SH)
(displayed at voltage input)
Min. value of PV input
scale
(SL)
(displayed at voltage input)
Selection of PV input
OFF
burnout action
1: Up scale
2: Down scale
(BSL)
Presence/absence of
OFF, ON
PV input reference
(RJC)
junction compensation
User setting
Retransmission output
OFF: Does not work.
type
1: PV
4: Loop power supply for sensor (15 V)
(RET)
Max. value of
RET=1: RTL + 1 digit to 100.0% of PV
retransmission output
input range
(RTH)
scale
Min. value of
RET=1: 0.0% of PV input range to
retransmission output
RTH - 1 digit
(RTL)
scale
DI function selection
OFF: The external contact input is disabled.
1: Resets the values of the PEAK and BOTM
operating parameters to an off-to-on transition
(DIS)
of the DI1 input.
SELECT display-1
OFF, 201 to 1015
registration
For example, registering "231" for C.S1 allows you to
(C.S1)
change alarm-1 setpoint in operating display.
SELECT display-2
registration
Numbers for registering alarm SP parameter for
(C.S2)
operating display:
SELECT display-3
Alarm-1 setpoint: 231 Alarm-2 setpoint: 232
registration
Alarm-3 setpoint: 233 Alarm-4 setpoint: 234
(C.S3)
SELECT display-4
registration
(C.S4)
Key lock
OFF: No key lock
1: Change to any parameter prohibited
(LOCK)
Prohibits any operating parameter or setup
parameter from being changed. The setpoint
of the LOCK parameter itself can be changed,
however.
2: Change to and display of operating parameters
prohibited
Turns off the display for setting operating
parameters, thus prohibiting any change to
the parameter settings.
(Press the SET/ENT key for more than
3 seconds to show the password check
display.)
Password setting
0: Password not set
1 to 9999
(PWD)
List of Alarm Types
The table below shows the alarm types and alarm actions.
In the table, codes 1, 2, 9, and 10 are not provided with stand-by actions, while codes 11, 12, 19, and 20 are provided with
stand-by actions.
Initial Value
User Setting
Alarm type code
Alarm action
Alarm type
OFF
Contact
closes
"Open/close" shows status of relay contact,
if alarm
and "lit" and "unlit" shows status of lamp
occurs
°C
No alarm
Hysteresis
1
Max. value of
PV high limit
Open (unlit)
Closed (lit)
instrument
11
input range
PV
Alarm setpoint
Hysteresis
2
Min. value of
instrument
PV low limit
Closed (lit)
Open (unlit)
input range
12
Alarm setpoint PV
1
Fault diagnosis output (Note1)
21
Note1: Fault diagnosis output
Turns on in case of input burnout, A/D converter failure, or reference junction compensation (RJC) failure.
Note2: FAIL output
100.0
Turns off in case of program failure, ROM failure, RAM failure, or power failure. This output is on during normal operation. If it turns
off, the retransmission output is set to 0%, the alarm output is set to OFF, and the indicator stops.
0.0
C
Stand-by Action
1
It is effective in the following cases where;
- the power is turned on
ON
- the alarm type is changed
1
100.0% of
PV input range
0.0% of
Power-on
PV input range
Behavior of the PV High-limit Alarm Parameter (Alarm Type Code: 1)
1
OFF
Alarm
setpoint
Off
On
Alarm
contact output
OFF
Useful Operating Display (SELECT Display)
Registering frequently changed parameters in the SELECT display after ordinary operating displays will allow you to
change settings easily. A maximum of four displays can be registered.
Useful
operating display
(SELECT display)
Ordinary operating
Setting method:
displays (example)
Set the parameter numbers (D register numbers) you wish to register for
setup parameters C.S1 to C.S4.
0
PV
PV
AL1
2
3
4
AL1
2
3
4
S E T / E N T
key
SET/ENT
SET/ENT
PV display
Alarm-1 setting
display (example)
S E T / E N T
key
Numbers for Registration with SELECT Display
Operating Parameter
Registration Number
Alarm-1 setpoint (A1)
231
Alarm-2 setpoint (A2)
232
Alarm-3 setpoint (A3)
233
Alarm-4 setpoint (A4)
234
Bias (BS)
243
Filter (FL)
244
Alarm type code
Alarm action
Alarm type
Contact
Contact
Contact
opens
closes
opens
"Open/close" shows status of relay contact,
if alarm
if alarm
if alarm
and "lit" and "unlit" shows status of lamp
occurs
occurs
occurs
OFF
Hysteresis
9
De-energized
Closed
Open (lit)
on PV high limit
(unlit)
PV
Alarm setpoint
19
Hysteresis
10
De-energized
Closed
Open (lit)
on PV low limit
(unlit)
20
Alarm setpoint
PV
FAIL output (Note2)
22
Normal
Abnormal
Treated
The alarm
as normal
output turns on.
Low limit of
alarm setpoint
The alarm output does not
turn on in this region even
if the PV value is below the
low limit of the alarm setpoint.
Time
PV value
Alarm hysteresis
Off
Setup Parameter
Registration Number
Alarm-1 hysteresis
919
Alarm-2 hysteresis
920
Alarm-3 hysteresis
921
Alarm-4 hysteresis
922
IM 05F01D02-03E (2)

Advertisement

loading

This manual is also suitable for:

Um330