C. Operational mode
The operating mode mentioned corresponds to standard user
situations. Refer to the manufacturer's instructions for specific
advice on the product used.
Application
- Depending on the product, the boiler must be cold or heated.
Refer to the instructions supplied with the product.
- Direct application to the heating surfaces with aerosol sprays.
- The concentrates are diluted in the proportions 1/5 to 1/20
(depending on the product and the condition of the boiler).
- Application with the spray is done in the upper part of the boiler
and on the walls of the combustion chamber. Surfaces are
dampened but not washed. It is not necesaary to use the spray to
get between the heating surfaces.
- A volume of one litre of solution is generally used for 1 m
heating surface (domestic boiler), i.e. 0.05 to 0.2 l of concentrate.
D. Ignition
The burner is ignited after allowing the product time to penetrate
for 2 to 5 min. Refer to the instructions supplied with the product.
E. Cleaning
- Remove the baffle plates.
- Light sweeping will remove the pulverent residues remaining
after combustion.
- The remaining pulverent residues are easy to remove by sweeping
or vacuum cleaning.
For certain products, brief application after cleaning has a
preventive effect, limiting deposits on the heating surfaces.
- Replace the baffle plates.
- Close the door of the combustion chamber.
- Service the burner.
- Replace the front panel.
7.1.3

Cleaning the casing material

Use a soapy solution and a sponge only. Rinse with clean water and
dry with chamois leather or a soft cloth.
18/03/2016 - 300020192-02
2
of
PK 550
7. Checking and maintenance
23