4. Installation

4.4 Chimney connection

The high-performance features of modern boilers and their use in
specific conditions as a result of the advance in burner technology
(e.g. first-stage or low modulation range operation) lead to very low
flue gas temperatures (<160°C).
4.4.1

Flue size

Refer to applicable regulations while determining the size of the flue.
Please note that PK 550 boilers have pressurised and tight furnaces
and that the pressure at the connection to the chimney must not
exceed 0 mbar, unless special sealing precautions have been taken,
for instance in order to connect a static condenser/regenerator.
4.4.2
Chimney connection
The connection shall be removable, and offer minimum load losses,
i.e. it must be as short as possible with no sudden change in section.
Its diameter shall always be at least equal to that of the boiler outlet,
i.e.:
Ø 300 mm for 9 sections
Ø 350 mm for 10 to 13 sections
Ø 400 mm for 14 to 20 sections
Boilers with 21 to 25 sections are supplied with a plain plate. The
maximum cut-out dimensions are 500 x 700 mm.
Fit a measuring point (Ø 10 mm hole) on the flue, in order to adjust
the burner (combustion check).
PK
PK
PK
Boiler
550-
550-
550-9
10
11
Ø F
300
350
350
K
5
26
27
*Dimension representing the end of the 100 mm long chimney
connection.
Note: with models PK 550-21, PK 550-22, PK 550-23,, PK 550-24
and PK 550-25, a plain plate which must be cut out is supplied
without the 100 mm chimney connection.
16
PK
PK
PK
PK
PK
550-
550-
550-
550-
550-
12
13
14
15
16
350
350
400
400
400
48
49
10
-19
-18
For this reason:
- Use flue gas pipes designed to enable the flow of condensates
which may result from such operating modes in order to prevent
damage to the chimney.
- Install a draining tee at the bottom of the chimney.
The use of a draught moderator is recommended as well.
PK
PK
PK
PK
PK
550-
550-
550-
550-
550-
17
18
19
20
21
400
400
400
400
3
4
25
-24
-23*
PK 550
PK
PK
PK
PK
550-
550-
550-
550-
22
23
24
25
Plain plate
-2*
-1*
20*
21*
18/03/2016 - 300020192-02

Advertisement

Table of Contents
loading

Related Products for OERTLI PK 550

Table of Contents