Lennox MPA018S4M-*P Installation Instructions Manual page 10

Multi-zone mini-split outdoor units mpa series,mpb series and mla series
Hide thumbs Also See for MPA018S4M-*P:
Table of Contents

Advertisement

INDOOR UNIT
NOTE - Minimum Line Set
Length - 10 ft. (3 m) per
Indoor Unit
NOTE - Maximum Line Set
Length Includes ALL
piping in measurement
Maximum Line Set
Furthest Indoor Unit
INDOOR UNIT
INDOOR UNIT
Outdoor Unit Model No.
Maximum Number of
Indoor Units
Indoor Unit Connections -
Liquid / Gas
Total Length of All Piping
Maximum Line Set
Length - Furthest Indoor
Unit
INDOOR UNIT
INDOOR UNIT
MPA018S4M-*P
MPB018S4M-*P
MLA018S4M-*P
Two
(2) 1/4 / 3/8
98 ft. (30 m)
66 ft. (20 m)
Figure 20. Multi-Zone Systems with All Indoor Unit Models
Maximum
Elevation -
Outdoor Unit
BELOW
Indoor Units
OUTDOOR UNIT
33 ft. (10 m) for MPA
49 ft. (15 m) for MLA and MPB
Maximum
Elevation -
Outdoor Unit
ABOVE Indoor Unit
MPA030S4M-*P
MPB030S4M-*P
MLA030S4M-*P
Three
(3) 1/4 / 3/8
148 ft. (45 m)
82 ft. (25 m)
10
49 ft.
(15 m)
NOTE - Maximum Difference
in Elevation Between
Indoor Units - 33 ft. (10 m).
MPA036S4M-*P
MPB036S4M-*P
MLA036S4M-*P
Four
(3) 1/4 / 3/8
(1)1/4 / 1/2
197 ft. (60 m)
98 ft. (30 m)
MPA048S4M-*P
MPB048S4M-*P
Five
(3) 1/4 / 3/8
(2) 1/4 / 1/2
246 (75 m)
98 ft. (30 m)