Huawei SUN2000-42KTL User Manual page 79

Hide thumbs Also See for SUN2000-42KTL:
Table of Contents

Advertisement

SUN2000-(36KTL,42KTL)
User Manual
Figure 6-8 Quick Settings screen (logging in as an advanced user)
Issue Draft A (2016-05-30)
Set the power grid code that applies to the country or region where the power station is located and
the inverter model.
Set user parameters based on the current date and time.
Set Baud rate, Protocol, and Address based on site requirements. Baud rate can be set to 4800,
9600, or 19200. Protocol can be set to MODBUS RTU, and Address can be set to any value in the
range of 1 to 247.
When multiple inverters communicate with the SmartLogger1000 or SmartLogger2000 over RS485,
the addresses for all the inverters on each RS485 route must be within the address range set on the
SmartLogger and cannot be duplicate. Otherwise, the communication will fail. In addition, the baud
rates of all the inverters on each RS485 route must be consistent with the SmartLogger baud rate.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 System Commissioning
73