Summary of Contents for Vaventis fresh-r On-The-Wall

  • Page 1 On-The-Wall Installation manual IMPORTANT: Read this manual carefully before installing the fresh-r®! Keep this manual for future use.
  • Page 2 Installation manual Foreword Installation manual for the contractor Dear contractor, Thank you for purchasing the fresh-r On-The-Wall or the fresh-r everywhere On-The-Wall . ® ® This manual is intended for professionals and contains all the necessary installation information. To install the fresh-r correctly and safely, it is essential that you read this information carefully ®...
  • Page 3: Table Of Contents

    Contents Intended use Target group Symbols used in this manual Safety symbols Other symbols General safety instructions Main components Tools needed for the installation How to install the fresh-r ® Connect the fresh-r to the internet ® Installation checklist 10. Specifications Who can I contact for questions, spareparts or more information? 12.
  • Page 4: Intended Use

    1. Intended use The fresh-r On-The-Wall is a decentral ventilation unit with heat recovery. The fresh-r takes ® ® heat from the stale air it expells and uses it to warm up the fresh air it brings in from outside. It improves air quality for a healthy indoor air quality and at the same time reduces your energy bill.
  • Page 5: General Safety Instructions

    4. General safety instructions DANGER • Connecting the fresh-r to the mains electricity supply must be done by a qualified ® electrician. • Risk for electric shocks or electrocution. Turn off the mains electricity supply in the distribution box before connecting the fresh-r electrically.
  • Page 6: Tools Needed For The Installation

    fig. 2 Main components Fresh air input socket, with fan (for upper duct pipe) Stale air output socket (for lower duct pipe) 6. Tools needed for the installation • Equipment to drill 2 round holes (Ø 160 mm) in the wall (typically water-cooled diamond core drill) •...
  • Page 7 2 Prepare the wall You will need two round holes (Ø 160 mm) in the outer wall of the building, for the air pipes; the lowest hole needs to have a slope of 2 degrees. You also need four holes in order to attach the fresh-r on the wall with four screws 6 x 120.
  • Page 8 The big holes To drill the lower big hole (160 mm), do the following: Drill through the outer wall(s) at a downward angle of 2 degrees. This is to allow the condensate to drain towards outside. To drill the upper big hole (160 mm), do the following: Drill straight through the wall(s).
  • Page 9 243 mm 105 mm 111 mm 1055 mm fig. 6 Check the dimensions of the corner holes before drilling...
  • Page 10 3 Cut the duct pipes NOTICE Make sure if you cut the duct pipes, the part you want to keep has a lip. To cut the duct pipes, do the following: Remove the EPP covers. Cut the upper duct pipe (input fresh air) to the total width of the wall (D1) + 15 mm.
  • Page 11 4 Place the duct pipes in the Unibody NOTICE Use the provided EPP glue for the lower duct pipe. The lower duct pipe is the condensate drain and needs to be water tight. Apply PVC glue to the last 3 cm of the duct and to the white ring.
  • Page 12 Put EPP glue on the Unibody around the PVC duct pipes Epp glue Epp glue fig. 11 Put EPP glue on the Unibody around the PVC duct pipes Place the EPP covers on the duct pipes. fig. 12 Place the EPP covers...
  • Page 13 Put EPP glue around the edges of EPP covers of the upper duct pipe and the lower duct pipe. NOTICE The connection of the lower duct pipe and the upper duct pipe to the Unibody needs to be airtight because air leaks can create unwanted condensation. Epp glue Epp glue fig.
  • Page 14 5 Mount the Unibody on the wall Remove the four corner bolts (don’t remove the middle bolts). Remove the four corner bolts DON’T remove the two middle bolts fig. 16 Remove the four corner bolts Put expanding foam around the edge of both EPP covers. Make sure the expanding foam insulate the whole edge of the EPP covers in order to prevent air leaking (regarding the inner wall).
  • Page 15 fig. 18 Press the two storm flap levers The following steps need to be done by two persons. First read step 5, 6 and 7 so you are well prepared. Then perform the actions. CAUTION Be carefull with the door. Giving too much pressure can damage the door or it’s hinges. DON’T apply force to the the door, when raising the fresh-r...
  • Page 16 The first person: Hold the Unibody as shown in fig. 20. Place the Unibody with the upper duct pipe and lower duct pipe in the wall. See fig. 21. CAUTION Hold the Unibody till it’s mounted with the four 6 x 120 screws. ...
  • Page 17 Seal between the EPP cover and the outer wall with outdoor silicone kit. Make sure you use enough expanding foam . Make sure the connection between the pipes and the outer wall is airtight. This will prevent air leaking. (outside of the house) fig.
  • Page 18 Turn the main electricity supply ON again at the distribution box. Turn the fresh-r ON and wait for approximately 1 minute while the unit boots up. ® If you see three illuminated lights and notice fans running, the unit is properly functioning.
  • Page 19 fig. 25 Lip should overlap with the edge of the grilles...
  • Page 20: Connect The Fresh-R To The Internet

    8. Connect the fresh-r to the internet ® By connecting the fresh-r to the internet you will benefit from automatic sotware updates. You will ® also have access to data graphs showing actual performance values of the air temperature and quality.
  • Page 21 10. Press refresh List. A list with Available Access Points will show. Select your own router by its name. NOTICE If your router name has spaces in it: for example “my router”, the connection will fail. In that case, please change the name (SSID) of your router to, for example, myrouter.
  • Page 22: Installation Checklist

    9. Installation checklist Use the following checklist after you have completed the installation. For a properly functioning fresh-r , please make sure you can answer all questions with ‘yes’. ® Check the following More information Are the 4 mounting screws properly functioning? Page 16 step 6.
  • Page 23: Specifications

    T +31 294 261 171 www.vaventis.com 12. Warranty 2 years as stated in the General terms and conditions of Vaventis B.V. The warranty period will be Extended with one year (3 years in total) if the fresh-r is connected ®...
  • Page 24: Frequently Asked Questions

    13. Frequently asked questions Before installing Where is the air extracted from the room? From the top of the door. What size building can one fresh-r ventilate? ® Up to 100 m , but this depends on the size, Why should we not mount the unit close to the lay-out, number of people and the regulations, ground? ask your supplier for details.
  • Page 25 Does the upper duct pipe need to be positioned in a How can I operate the unit? 2 degree angle? On the control panel, “A” for automatic. No, this can be level but it is no problem to You can increase or decrease the fan speed mount it under a 2 degree angle, the upper manually using the fan buttons.
  • Page 26: Declaration Of Conformity

    14. Declaration of conformity as required by EC Directive Vaventis b.v. The manufacturer: Achteromstraat 8a Address: 1381 AV Weesp, The Netherlands declare under our sole responsibility that the following product Air handling unit with heat recovery E quipment: Vaventis Brand name:...
  • Page 27: Appendix

    15. Appendix 15.1 Technical drawings 15.1.1 fresh-r ® (Dimensions are in mm. Dimensions in brackets are in inches).
  • Page 28: Fresh-R ® With Rectangular Duct On Top

    15.1.2 fresh-r with rectangular duct on top ® (Dimensions are in mm. Dimensions in brackets are in inches).
  • Page 29: Outer Wall Template

    15.1.3 Outer wall template (Dimensions are in mm. Dimensions in brackets are in inches).
  • Page 30: Fresh Air Everywhere ® : Connect To Your In-House Ventilation System

    15.2 Fresh air everywhere : connect to your in-house ventilation system ® The fresh-r everywhere is designed to be part of your in-house ventilation system. By ® mounting the extract ducts to the fresh-r everywhere you can establish this connection. ®...
  • Page 31: Rectangular Duct Dimensions

    15.2.1 Rectangular duct dimensions (Dimensions are in mm. Dimensions in brackets are in inches). [2,362] [ 2.362 ] [3,937] [8,032] [ 3.937 ] [ 8.032 ] 15.2.2 Rectangular right angle duct dimensions 258,75 104,5 [10,187] 2 places [4,114] 2 places [1,969] [8,071] [2,402]...
  • Page 32: Rectangular Ro Round Duct Dimensions

    15.2.3 Rectangular ro round duct dimensions (Dimensions are in mm. Dimensions in brackets are in inches). [4,724] [4,961] [8,661]...
  • Page 36 © 2015 by Vaventis B.V. All right reserved...