Control Characteristics - Viessmann VITOTROL 100 Operating Instructions Manual

Room thermostat type utd
Table of Contents

Advertisement

Further adjustments
Wall adjustment
(cont.)
5. a/b until the required compen-
sator is displayed.
6. d
to confirm.

Control characteristics

The hysteresis controller is factory-set. The hysteresis value influences the
starting and stopping point for "Heating" or "Not heating".
Example:
Set room temperature: 21 °C
Hysteresis: 0.6 °C
Heating stops as soon as the actual
room temperature exceeds 21.3 °C.
Heating starts as soon as the actual
room temperature falls below
20.7 °C.
You can change the control character-
istics by changing the hysteresis
value. In the delivered condition, the
hysteresis is set to 0.6 °C. Select a
lower value if your system responds
too slowly.
Turn the rotary program selector to
"MENU" and press the following keys:
1. a/b until "SERVICE" is dis-
played; symbol "Ä"
flashes.
2. d
to confirm, "DISPLAY"
flashes.
3. a/b until "CONTROL" is dis-
played.
4. d
to confirm, "HYST CON-
TROL" flashes.
24
7. Turn the rotary selector to the
required program.
5. d
to confirm; "HYSTERESIS"
is displayed.
6. a/b until the required value is
displayed.
Setting range:
0.2 to 1.0 °C
7. d
to confirm; "END" is dis-
played.
8. Turn the rotary selector to the
required program.