WARNING: Do not pack required air space (clearance) with insulation or other materials. When non-
!
combustible building materials contact the body of the oven, the clearances to combustibles are
transferred to those non-combustibles.
INSTALLATION CLEARANCES
The Wood Stone gas-fired Tandoor must be installed with at least 25mm
(1") side clearance to combustible construction� Install the unit on a
non-combustible floor, or one provided with a non-combustible covering
that extends at least 92mm (36") in all directions� Any combustible
construction above (overhanging) the appliance should be protected in
a manner acceptable to the authority having jurisdiction�
ENCLOSURES
If the appliance is enclosed, provisions should be made so that it can
easily be removed from the enclosure�
VENTING
The Wood Stone gas-fired Tandoor must be installed under an appropriate grease rated exhaust hood� Refer to local and/or national
codes for hood specification requirements� The hood must be designed for the removal of the combustion products of gas, as well
as the cooking vapors related to the intended use of the oven� Make up air must be provided as necessary for the proper operation
of the ventilation system�
Some jurisdictions may require that the Tandoor be interlocked to the hood ventilation system to prevent operation of the appliance
when the ventilation system is not turned on� If an interlock is required, use an approved gas solenoid (supplied and installed by
others), wired so that the gas supply to the appliance is turned off whenever the ventilation system is turned off�
M0054.05 APRIL 2017
An ongoing program of product improvement may
require us to change specifications without notice.
8
PG
OF
16
CLEARANCES & VENTING
Shaded area must be left unobstructed for
critical combustion air and easily accessible
for removal of the drip pan and operation
of the pilot safety valve. If this area must
be covered, the cover should be easily
removable and heavily perforated.
WOOD STONE CORPORATION
1801 W. Bakerview Rd.
Bellingham, WA 98226 USA
Tandoor CE Installation
and Operation Manual
Combustible construction overhanging
the appliance should be protected in
a manner acceptable to the authority
having jurisdiction.
Install on a noncombustible floor, or one
protected in a manner acceptable to the
authority having jurisdiction, extending
92mm (36") in all directions.
+1.360.650.1111
TEL
+1.360.650.1166
FAX
25mm (1") side
clearance to
combustible
construction
info@woodstone-corp.com
E-MAIL
woodstone-corp.com