Advantech ADAM 4100 User Manual page 98

Industrial grade data acquisition modules
Hide thumbs Also See for ADAM 4100:
Table of Contents

Advertisement

Command Set
4.6.21
@AACACj
Name
Clear Latch Alarm
Description
Both alarm states (High and Low) of the counter module
are set to OFF.
Syntax
@AACACj(cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter module.
CA is the Clear Latch Alarm command
(cr) represents terminating character, carriage return (0Dh)
Response
!AA(cr) if the command was valid
! is a delimiter character indicating that a valid command
was valid
AA represents the 2-character hexadecimal address of the
responding counter module.
(cr) represents terminating character, carriage return (0Dh)
Example
command: @05CAC1(cr)
response:
The counter module at address 05h and channel 1 are
instructed to set both alarm states (High and Low) to OFF.
The module confirms the execution.
4-60 ADAM 4100 Series User's Manual
Cj is the channel j
?AA(cr) if an invalid command has been issued.
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
!05(cr)