4.6.20
$AAERFFcc
Name
Read DO current pulse output counts
Syntax
$AAERFFcc (cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address which is to be accessed.
ERFF is the DO current pulse output counts command
cc is the channel number ( 00~07 means Ch0~Ch7)
(cr) is the terminating character, carriage return (0Dh).
Response
>AAmvvvvvvvv if the command was valid.
?AA(cr) if an invalid command has been issued.
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
> is a delimiter character indicating that a valid command
was received.
m: 0 means non-continue mode
vvvvvvvv: 8-hex character pulse output value. When it is set
to 0, it will operate as continuous pulse output
? is a delimiter character indicating that the command was
invalid.
AA (range 00-FF) represents the responding 2-character
hexadecimal address of the digital I/O module.
1 means continue mode
Chapter
Chapter 4 Command Set 4-59
4