9.3.12
Temperature protection of compressor discharge
Temperature protection of
compressor discharge
Check whether the
compressor discharge temp.
is more than 115° C ?
No
Check whether the wiring
connection is right between
compressor discharge temp.
sensor and PCB according
to wiring diagrams?
Yes
Judge: The
discharge temp.
sensor is broken
Method: Check whether the
resistance of compressor
discharge temp. sensor is
right refer to the Appendix 2
Yes
Replace outdoor main board
Check whether the
Yes
refrigerant is leak
No
Correct the wiring connection
No
Replace the compressor discharge temp. sensor
52
Yes
Stop leaking and add refrigerant
Trouble is solved