Midea MFE-60ARN1-RB4W Service Manual page 40

Floor standing type
Table of Contents

Advertisement

The others modes:
Condition
T1-Ts≥1° C and compressor is off reac
hes up to over 3 minutes
Ts-T1>1° C
When compressor is on, outdoor fan will follow the below rules:
When T3≥33℃, the two fan run at the same time.
When T3≤30℃, the above fan is on, the below fan is off.
8.3.3.2 Action of Indoor Fan
HIGH/ MED /LOW/AUTO fan can be switched over by your comfort.
Auto fan under cooling mode.
MFE-60ARN1-RB4W(2T0043800036)
The others modes:
Condition
T1-Ts≥4° C
2° C≤ T1-Ts < 4° C
T1-Ts < 2° C
8.3.3.3 Low evaporator coil temperature T2 protection
MFE-60ARN1-RB4W(2T0043800036)
AC will enter T2 protection if any of the following conditions is satisfied.
Condition 1:
5.0
High
4.0
Medium
3.0
2.0
Low
Fan speed
High
Med
Low
T2
On
T2CoolExit
T2CoolIn
Off
37
Compressor and outdoor fan
On
Off