Siemens BACnet Owner's Manual page 16

Fume hood controller vertical sash with damper or venturi air valve and 2-position constant volume with damper
Hide thumbs Also See for BACnet:
Table of Contents

Advertisement

Chapter 3 – Point Database
Descriptor
Address
EXH VOL
FLOW COEF
DUCT AREA
TRANS RANGE
LINEAR FL RG
AVS2 PRESS
DI 2
DI 2 STPT SW
DI 6
AO 1
AO 3
EXH AO3
EXH DO1
DO 1
RETC DO 2
DO 2
DO 3
DO 4
DO 5
HI.LOW DO5
DECOM DO6
DO 6
ALARM DO7
16
Siemens Industry, Inc.
Building Technologies
Application
1
31
All
32
All
33
All
34
6740, 6741, 6742
35
6740, 6741, 6742
36
All
37
6741, 6742, 6700
37
6740
38
All
39
All
40
6740, 6741, 6700
40
6742
41
6740, 6741
41
6742, 6700
42
6740, 6741
42
6742, 6700
43
All
44
All
45
6741, 6742, 6700
45
6740
46
6740, 6741, 6742
46
6700
47
6740, 6741, 6742
Owner's Manual
Description
ALRT AREA or AT ALRT AREA depending on the state of
ATTN.UNATTN.
The calculated value, in CFM (LPS), of the exhaust airflow.
Gain factor for the flow sensor.
Area of the duct, in square feet (SQM), where the air velocity
sensor is located.
The maximum range, in inches of water (PA), of the
differential pressure transmitter. Standard values are 0.1
(25.3), 0.25 (62.275), 0.5 (124.55), and 1.0 (253).
When AI 3 is used as a linear flow sensor input, this value is
the maximum range of the input.
The pressure that is applied to AVS2.
Actual status of a contact connected to the controller at DI 2.
ON indicates that the contact is closed; OFF indicates that
the contact is open. If a wall switch is used, it is connected to
DI 2.
Digital input for dry contact connection to control the HI/LOW
flow setpoint of the controller.
Actual status of a contact connected to the controller. ON
indicates that the contact is closed; OFF indicates that the
contact is open. Actual status of a contact connected to the
controller. ON indicates that the contact is closed; OFF
indicates that the contact is open.
Spare analog output is a 0 to 10 Vdc output.
Spare analog output is a 0 to 10 Vdc output.
Control signal for Venturi General Exhaust Valve (0 - 10V).
Digital output 1 and 2 are used to control a floating point
actuator.
Spare digital output controls a 24 Vdc load with an ON or
OFF status.
Digital output 1 and 2 are used to control a floating point
actuator.
Spare digital output controls a 24 Vdc load with an ON or
OFF status.
Spare digital output controls a 24 Vdc load with an ON or
OFF status.
Spare digital output controls a 24 Vdc load with an ON or
OFF status.
Spare digital output controls a 24 Vdc load with an ON or
OFF status.
Digital output that follows the HI/LOW flow setpoint.
Digital output that turns on when a decommissioned hood is
used.
Spare digital output controls a 24 Vdc load with an ON or
OFF status.
Intended to drive local alarm device (horn, light, and so on.).
Function set up by setting alarm enable points.
125-5093