2.6

Temperature sensor characteristics

When measuring temperature sensors, observe the following
requirements:
Isolate the system before measuring.
Measure the resistance at the cable ends.
The resistance values represent average values and are
subject to tolerances.

°C
°C
20
14772
50
25
12000
55
30
9786
60
35
8047
65
40
6653
70
45
5523
75
Table 3
Temperature sensor measurements (all temperature
sensors in solar system except collector temperature
sensors)


°C
°C
– 30 364900 25 20000
– 20 198400 30 16090
– 10 112400 35 12800
0
40 10610 100 1344 180
66050
5
50000
50 7166
10
40030
60 4943
15
32000
70 3478
20
25030
75 2900
Table 4
Collector temperature sensor measurements
2.7

Additional accessories

For precise information regarding suitable accessories, refer to
the manufacturer's product literature.
Function modules and user interfaces of the control system
EMS 2:
MS 100: Module for solar system
MS 200: Module for extended solar systems.
CS 200 – 6720830475 (2015/06)
9 mA
EMS 2
0 °C to 50 °C
III
IP20


°C
4608
80
1704
3856
85
1464
3243
90
1262
2744
95
1093
2332
100
950
1990


°C
°C
80
2492 150
364
90
1816 160
290
95
1500 170
233
189
110 1009 190
155
120
768
200
127
130
592
140
461
2.8

Disposal

▶ Dispose of packaging in an environmentally responsible
manner.
▶ When replacing assemblies or components, dispose of the
old assemblies or components in an environmentally
responsible manner.
3

Installation

CAUTION:
Risk of injury through scalding!
If the DHW temperature is set to > 60 °C, discharging unmixed
domestic hot water can lead to serious scalding.
▶ Set the temperature for normal operation to < 60 °C.
▶ Do not discharge domestic hot water unmixed.
▶ Install a mixer.
WARNING:
Risk to life from electric shock!
Touching live parts can result in an electric shock.
▶ Before installing accessories: Disconnect the power supply
to the heat source, building management system and any
other BUS nodes (all poles) and secure against
unauthorised or accidental reconnection.
3.1

Types of installation

The installation of the solar controller depends on its use and
the solar heating system design ( Chapter 2, page 4).
3.2

Installation location of the solar controller

For direct and easily accessible operation we recommend the
installation of the solar controller in the living space.
3.3

Installation in the reference room

The installation surface on the wall must be flat.
▶ Install wall-mounting plate ( Fig. 3).