EDUS091617 Power Supply 1. Power Supply Indoor Unit Outdoor Unit Power Supply FFQ09Q2VJU RX09QMVJU 1 phase, 208 - 230 V, 60 Hz FFQ12Q2VJU RX12QMVJU FFQ15Q2VJU RX15QMVJU Note: Power Supply Intake; Outdoor Unit Split Type Air Conditioners FFQ-Q Series...
R/C with back light Wired (option) 1: With wired remote controller Note: : Available 2: With wireless remote controller — : Not available 3: With air direction adjustment grille (option) 4: Receiving sound only Split Type Air Conditioners FFQ-Q Series...
EDUS091617 Dimensions 4. Dimensions Indoor Unit FFQ09/12/15Q2VJU with BYFQ60B3W1 (Decoration Panel) 3D106040 FFQ09/12/15Q2VJU with BYFQ60C2W1W(S) (Decoration Panel) 3D106039 Split Type Air Conditioners FFQ-Q Series...
Page 10
BETWEEN REMOTE EX.) KJB111A EX.) KJB211A CONTROLLER AND (OPTIONAL ACCESSORY) (OPTIONAL ACCESSORY) CONTROL BOX SWITCH BOX LOWER CASE PORTION LOWER CASE PORTION [FIELD SUPPLIED PART] 3D091305A BRC082A41W — Wireless Remote Controller (Option) — 3D082556A Split Type Air Conditioners FFQ-Q Series...
Page 11
EDUS091617 Dimensions BRC082A42W(S) — Wireless Remote Controller (Option) — 3D082024 Split Type Air Conditioners FFQ-Q Series...
STOP VALVE CONNECTION WITH DRAIN JOINT) (φ1/2 (φ12.7) CuT) 1-15/16 (50) 1-15/16 (50) 1-15/16 (50) SERVICE PORT UNIT: inch (mm) 6-13/16 (173) IN CASE OF REMOVING STOP VALVE COVER AND C: 3D092224A TERMINAL STRIP COVER Split Type Air Conditioners FFQ-Q Series...
RECEIVER ON: HEATING DISCHARGE PIPE THERMISTOR FIELD PIPING MUFFLER (1/4 CuT) 1/4 CuT LIQUID STOP VALVE MUFFLER 1/2 CuT FIELD PIPING ACCUMULATOR 5/16 CuT (1/2 CuT) GAS STOP VALVE WITH SERVICE PORT COMPRESSOR 3D092220A Split Type Air Conditioners FFQ-Q Series...
15 Class (R-410A) Range of the refrigerant additional charge 16.4 32.8 49.2 65.6 82.0 98.4 (ft) 30 (m) Piping length Note: The graphs show the factor when additional refrigerant of the proper quantity is charged. Split Type Air Conditioners FFQ-Q Series...
57.2 68 73.4 82.4 Indoor temp. (˚FWB) Notes: The raphs are based Indoor temp. (˚FDB) on the followin conditions. • Equivalent pipin len th 25ft • Level difference 3D092209A • Airflow rate Hi h Split Type Air Conditioners FFQ-Q Series...
2. The data are based on the conditions shown in the table below. Cooling Heating Piping Length Indoor ; 80°FDB (26.7°CDB) / Indoor ; 70°FDB (21°CDB) / 67°FWB (19.4°CWB) 60°FWB (15.6°CWB) 16.4 ft (5 m) Outdoor ; 95°FDB (35°CDB) Outdoor ; 47°FDB (8.3°CDB) Split Type Air Conditioners FFQ-Q Series...
Heatin APPROXIMATE APPROXIMATE NC-20 THRESHOLD HEARING THRESHOLD HEARING NC-20 FOR CONTINUOUS FOR CONTINUOUS NOISE NOISE 3D106127 1000 2000 4000 8000 1000 2000 4000 8000 OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz) Split Type Air Conditioners FFQ-Q Series...
: Indoor fan motor malfunctioning of the ground leak detector.) : Fan motor rated output (W) : Full load amps (A) 3D106058 Split Type Air Conditioners FFQ-Q Series...
Installation Lid of installation box KRP1BA101 (Optional accessory) Adaptor (KRP4A74) PCB support Installation box for adaptor PCB KRP1BA101 (Optional accessory) Note: Installation box for adaptor PCB is required to install the adaptor. 1P161220-1A Split Type Air Conditioners FFQ-Q Series...
Low voltage wires and high voltage wires should be kept space at least 50 mm from each other. Adaptor PCB Low voltage wire PCB support (Accessory of adaptor) Hole for low voltage wire (Signal line) Hole for high voltage field wire Installation box 1 Split Type Air Conditioners FFQ-Q Series...
Page 168
Connect wires with the control box. (Refer to the installation manual attached to the adaptor.) • After connecting wires with the control box, clamp wires by using the cord stickers 5 and the clamp 3 as shown in the below drawing. Clamp 3 Cord sticker 5 1P107687-1D Split Type Air Conditioners FFQ-Q Series...
2 Remove the cover pushig up the nail to the cover of the sensor box. about 6mm width flat blade screw driver <Cautions> Do not push the nail powerfully with a narrow flat blade screw driver, because you may break off the nail. Split Type Air Conditioners FFQ-Q Series...
Page 170
M3 (field supplied) and carry out the wiring. The length of insulation to be peeled off is as shown. (Work carefully so that the connector side may not be cut.) For M3 Round crimp terminal Split Type Air Conditioners FFQ-Q Series...
Provide protection of the existing cable for thermistor without affecting other components. 3) Fit the sensor box cover into the sensor box. Operation test after mounting the sensor Conduct cooling and heating operation test after the sensor is mounted and the wiring is completed. 3K019189-1D Split Type Air Conditioners FFQ-Q Series...
Adjust the height of the indoor unit. Be sure the piping will not contact with the ceiling joist etc. after adjusting the height. Standard installation When the Panel spacer is installed Hanger Hanger bracket bracket False ceiling False ceiling Split Type Air Conditioners FFQ-Q Series...
Install the decoration panel to the indoor unit according to the installation manual of decoration panel. The panel spacer is not firmly fixed to the decoration panel , so that never hold the panel spacer directly or lean the decoration panel extremely. 1P107764-1C Split Type Air Conditioners FFQ-Q Series...
1. Cut off the knockout hole on the side plate. ( Fig.1 ) The knockout hole is opposite to ref. pipe. Ref. pipe Knockout hole Drain pipe Side plate Fig.1 Cut it off with nipper. Slit Side plate Split Type Air Conditioners FFQ-Q Series...
Page 177
· Do not do the followings when installing duct. A ) To bend the duct excessively B ) To bend the duct too many times C ) To reduce the duct diameter WRONG WRONG WRONG 2P108307-1A Split Type Air Conditioners FFQ-Q Series...
Option List EDUS091617 13.18 <KPS063A47> Snow Hood (Outlet) Split Type Air Conditioners FFQ-Q Series...
Page 199
EDUS091617 Option List 3P436073-1 Split Type Air Conditioners FFQ-Q Series...
Page 204
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.