Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual page 25

19xrv pic iii control hermetic centrifugal liquid chillers
Table of Contents

Advertisement

To access this display from the ICVC default screen:
1.
Press MenU.
Press StAtUS.
.
Scroll down to highlight VFD_StAt.
3.
4.
Press SeLeCt.
DESCRIPTION
VFD Fault Code
Single Cycle Dropout
Line Current Imbalance
Line Voltage Imbalance
Line Phase Reversal
High Line Voltage
Low Line Voltage
High DC Bus Voltage
Low DC Bus Voltage
Motor Current Imbalance
Motor Overload
Rectifier Overcurrent
Rectifier Overtemp
Rectifier Power Fault
Inverter Overcurrent
Inverter Overtemp
Inverter Power Fault
Ground Fault
Frequency Fault
VFD Power on Reset
Start Complete
Stop Complete
Condenser High Pressure
Motor Amps Not Sensed
Start Acceleration Fault
Stop Fault
VFD Start Inhibit
VFD Checksum Error
VFD Comm Fault
VFD Fault
VFD Gateway Version #
VFD Inverter Version #
VFD Rectifier Version #
Note: All variables with CAPITAL LETTER point names are available for CCN read operation.
To access this display from the ICVC default screen:
1.
Press MenU.
.
Press StAtUS.
3.
Scroll down to highlight ICVC_pWD.
DESCRIPTION
Disable Service Password
**Remote Reset Option
Reset Alarm?
CCN Mode?
Note: The Disable Service Password parameter supports the service tool password disable access. It will only allow forcing with the service tool for a one time bypass of
both the service menu and the VFD config data table. Exit from the service menu reverts to normal password operation. Those with (**) shall support write operations for
ICVC only.
The Reset Alarm? and CCN mode? parameters support write operations from CCN and LEI devices when the Remote Reset Option is enabled.
Table 3 - ICVC display data (continued)
Example 7 - VFD_STAT display screen
STATUS
0 to 272
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 255
0 to 1000
0 to 1000
Example 8 - ICVC_PWD display screen
STATUS
0 to 1
0 to 1
0 to 1
0 to 1
UNITS
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
FALSE/TRUE
FALSE/TRUE
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
UNITS
DS/ENABLE
DS/ENABLE
NO/YES
NO/YES
POINT
VFD_FLT
CYCLE_1
LINEIM_I
LINEIM_V
PH_REV
HI_VOLT
LOW_VOLT
HI_DCBUS
LO_DCBUS
MOTIM_I
MOTOR_OV
RECT_OI
RECT_OT
RECT_PU
INV_OI
INV_OT
INV_PU
GRND_FLT
FREQFLT
VFD_POR
START_OK
STOP_OK
PRS_TRIP
NO_AMPS
ACCELFLT
AMPSTOP
STRT_INH
CHECKSUM
VFD_COMM
VFDFAULT
VFG_VER
INV_VER
REC_VER
POINT
PSWD_DIS
RESETOPT
REMRESET
REM_CCN
5