To access this display from the ICVC default screen:
1.
Press MenU.
Press StAtUS.
.
Scroll down to highlight CoMpReSS.
3.
4.
Press SeLeCt.
DESCRIPTION
Actual VFD Speed
**Target VFD Speed
Actual Guide Vane Pos
Guide Vane Delta
**Target Guide Vane Pos
Oil Sump Temp
**Oil Pump Delta P
Comp Discharge Temp
Comp Thrust Brg Temp
Comp Motor Winding Temp
Spare Temperature 1
Spare Temperature 2
Oil Heater Relay
Diffuser Actuator
Surge Protection Counts
Note: All variables with CAPITAL LETTER point names are available for CCN read operation. Those with (**) shall support write operations for ICVC only.
To access this display from the ICVC default screen:
1.
Press MenU.
.
Press StAtUS.
Scroll down to highlight HeAt_eX.
3.
4.
Press SeLeCt.
DESCRIPTION
**Chilled Water Delta P
Entering Chilled Water
Leaving Chilled Water
Chilled Water Delta T
Chill Water Pulldown/Min
Evaporator Refrig Temp
**Evaporator Pressure
Evaporator Approach
**Condenser Water Delta P
Entering Condenser Water
Leaving Condenser Water
Condenser Refrig Temp
**Condenser Pressure
Condenser Approach
VFD Coolant Flow
Hot Gas Bypass Relay
Surge/HGBP Active?
Active Delta P
Active Delta T
Surge/HGBP Delta T
Head Pressure Reference
Evaporator Saturation Temp
Note: All variables with CAPITAL LETTER point names are available for CCN read operation. Those with (**) shall support write operations for ICVC only.