Read Input Register 1011
var106 – Calibration type (8-bit enum)
Request Message
Address
Function
Starting Address Hi
Starting Address Lo
Quantity of Inputs Hi
Quantity of Inputs Lo
CRC
CRC
*Register Value = XX01h = Class1

1.3.4 RO String

Read only access to string types.
Each AquaMaster 3 String type requires 18 MODBUS Registers (36 bytes). Consequently, RO String
Register addresses are assigned at intervals of 18 and the Request Message must provide Quantity of
Inputs in multiples of 18.
Read Input Registers 2271 to 2288
var215 – Original Manufacturer
Request Message
Address
Function
Starting Address Hi
Starting Address Lo
Quantity of Inputs Hi
Quantity of Inputs Lo
CRC
CRC
MODBUS Tables Supplement COI/FET2XX/MOD/TBL-EN
(Hex)
Response Message
01
Address
04
Function
03
Byte count
f2
Register Value Hi*
00
Register Value Lo*
01
CRC
90
CRC
7d
(Hex)
Response Message
01
Address
04
Function
08
Byte count
de
byte0
00
byte1
12
byte2
12
byte3
5d
byte4
byte5
byte6
byte7
byte8
byte9
byte10
byte11
byte12
byte13
byte14
byte15
byte16
byte17
byte18
(Hex)
Error Message
01
Function
04
Exception Code
02
00
01
78
f0
(Hex)
=char
Error Message
01
Function
04
Exception Code
24
41
A
42
B
42
B
20
space
4c
L
69
i
6d
m
69
i
74
t
65
e
64
d
00
null
00
00
00
00
00
00
00
MODBUS Protocol
(Hex)
84
Exception Code
(Hex)
84
Exception Code
6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents