8) Phenomenon Observed After Shortcircuit, Wire Breakage On Sensor - Mitsubishi Heavy Industries SRK63ZR-S Technical Manual

Inverter wall mounted type residential air-conditioners split system air to air heat pump type
Hide thumbs Also See for SRK63ZR-S:
Table of Contents

Advertisement

Rotor lock
Service valve (gas side) closed operation

(8) Phenomenon observed after shortcircuit, wire breakage on sensor

(a) Indoor unit
Operation
Sensor
mode
Cooling
Room temperature
sensor
Heating
Cooling
Heat exchanger
sensor
Heating
Cooling
Humidity sensor
(1)
Heating
■ Humidity sensor operation
Failure mode
①②
Shortcircuit
Are the service valve (gas side)
opened ?
YES
Is the checked result of power
transistor module OK ?
YES
Is the space for installation of indoor and/or
outdoor unit enough ?
Is there any short circuit of air on indoor
and/or outdoor unit ?
Control input circuit resding
At heating, does the indoor fan motor run ?
Is the filter clogged ?
Is there any liquid flooding ?
Is there any anomalous sound on the
compressor?
YES
After resetting power for several
times does it become normal ?
YES
Temporary noise may cause of anomaly.
If noise source can be found, take
countermeasure.
See page 63.
Phenomenon
NO
Open the valve.
NO
Defective outdoor PCB
Air conditioning system operation
NO
Defective outdoor PCB

-
-
'15 • SRK-T-175
Defective compressor, defective
outdoor PCB
Service valve (gas side) closed,
Defective outdoor PCB
Disconnected wire
Replace.
Replace.