Mitsubishi Electric EHST20C-VM6HB Service Manual page 66

Cylinder unit
Hide thumbs Also See for EHST20C-VM6HB:
Table of Contents

Advertisement

Part Name
Booster heater
Thermostat (90 °C) and thermal cut out (11 °C)
121 °C
Thermal
cut-out
9
kW heater (0V, 1 phase)
 + 4kW heater (0V, 1 phase)
2kW
2kW
3
 + 6kW heater (400V,  phase)
2kW
4
5
Earth leakage circuit breaker for heater
Relay for heater
R
S
T
A1 A2
U
V
W
Flow switch
Flow
OCH531
90 °C
Manual reset
water
thermostat
10
2kW
2
1
2kW
4
1
2
2kW
1kW
2kW
1kW
1kW
6
1
2
3
1
2
3
Check Points
Measure the resistance between the terminals with a tester.
Terminal
110(±35)mΩ
9-10
Terminal
Normal
26.5(+3/-1.3)Ω
1-
Terminal
26.5(+3/-1.3)Ω
1-
13.3(+1.5/-0.6)Ω
-4
Terminal
Normal
105.8(+11.8/-5)Ω
1-=-=1-
52.9(+5.8/-2.5)Ω
4-5=5-6=4-6
If a short circuit occurs on the booster heater, immersion heater, or each power
line, a short-circuit breaker will trip and power source will be blocked.
Eliminate the causes of short circuit and then turn on the breaker again.
When the applied voltage is not 230V AC across the terminals A1-A2, check the
terminals R-U, S-V, and T-W are open.
When the applied voltage is 230V AC across the terminals A1-A2, check the
terminals R-U, S-V, and T-W are short.
Measure the resistance between the terminals with a tester.
State of moving part
Paddle vertical (Flow < 5.5 l/min)
Paddle inclined (Flow > 5.5 l/min)
66
Normal
Abnormal
Open or Short
Abnormal
Open or Short
Normal
Abnormal
Open or Short
Open or Short
Abnormal
Open or Short
Open or Short
Normal
Abnormal
Open
Other than open
Short
Other than short