3-9. CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH
(3) M-SERIES PIPING CORRECTION COOLING
Refrigerant piping length (ft)
25(std)
40
1.000
0.954
(4) M-SERIES PIPING CORRECTION HEATING
Refrigerant piping length (ft)
25(std)
40
1.000
0.989
Due to continuing improvement, above specification may be subject to change without notice.
MSZ-GE-36
2013 M-Series - MSZ-GE Heat Pump Systems (June 2013)
65
100
0.878
0.771
65
100
0.972
0.955
© 2013 Mitsubishi Electric US, Inc.