Rinnai E60SRN Installation & Service Instructions Manual page 41

Table of Contents

Advertisement

Using Indoor Air For Combustion
When using air from other room(s) in the building, the total volume of the room(s) must
be of adequate volume (Greater than 50 cubic feet per 1000 Btu/hr). Each combustion
air opening must have at least one square inch of free area for each 1000 Btuh, but
not less than 100 square inches each.
Using Outdoor Air For Combustion
Outdoor air can be provided to a confined space through two permanent openings,
one commencing within 12 in. (300mm) of the top and one commencing within 12"
(300mm) of the bottom, of the confined space. The openings shall communicate to
the outside by one of two ways:
directly through horizontal ducts
indirectly through vertical ducts
When communicating directly with the outdoors through horizontal ducts, each
opening shall have a minimum free area of 1 in
total input rating of all appliances in the confined space.
Note: If ducts are used, the cross sectional area of the duct must be greater than
or equal to the required free area of the openings to which they are connected.
When communicating indirectly with the outdoors through vertical ducts, each
opening shall have a minimum free area of 1 in
total input rating of all appliances in the confined space. Combustion air to the
appliance can be provided from a well ventilated attic or crawl space.
Gas Vent / Boiler Exhaust
OUTLET AIR DUCT
INLET AIR DUCT
Gas Vent / Boiler Exhaust
INLET AIR DUCT
[Ends 1Ft (300mm)
above floor]
Louvers and grills figure 21
BOILER
OUTLET
AIR
BOILER
/2000 Btu/hr (1100 mm
2
/4000 Btu/hr (550 mm
2
Gas Vent / Boiler Exhaust
OUTLET
AIR
BOILER
INLET
AIR
Ventilation Louvers for
unheated crawl space
/kW) of
2
/kW) of
2
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E85srnE110srnE85srpE60srpE110srpE60sr ... Show all

Table of Contents