Chapter 4: Functional Parameter Table

Here only simple parameter table. For details, pls read AC70 series manual or consult us.
"●":Means that the parameter can be revised during frequency inverter in a running state.
" ":Means that the parameter can not be revised during frequency inverter in a running state.
"×":Means that the parameters can only be read and can not be changed.
"–":Means that the parameter is only set by the manufacturer.
" ":Means that the parameter is related to the type of the frequency inverter
4.1 Basic parameter
Code
Fucntion name
funcion
Control method selection
E-00
Running control command
E-01
chanel selection
Frequency reference given
E-02
main channel selection
Setting range and definition
0: Open loop vector control without
PG
1: V/F control mode
0: Operator keypad
1: External terminal control
2: RS485 Communications port
control
0: Operator keypad digital given
1: Potentiometer of keypad
2: Terminal VS1 analog voltage 0-10V
3: Terminal AS analog current signal
4 20mA
4: Terminal VS2 analog voltage -10
10V
5: Pulse train signal
6: RS485 communication port
7: Up and Down control
8: General PID operation
9: Constant pressure PID control
10: Program running
11: Swing frequency run
12: Terminal selection:
15
pr
Refer
Factary
op
to
default
ert
page
y
1
69
0
69
1
69
Comm
unicati
on
code
100H
101H
102H