Terminal
Name
TA
Normally-open
contact
TC
Collector
Y
open output
Auxiliary
+24V
power output +
Auxiliary
COM
power output -
FWD
Forward
REV
Reverse
Multi function contact
X1
input X1
Multi function contact
X2
input X2
Multi function contact
X3
input X3
Multi function contact
X4
input X4
AO
Analog output
AS
Current analog input
VS
Voltage analog input
Signal
+10V
power terminal
Signal
GND
power terminal
Communication
A+
terminal A+
Communication
B-
terminal B-
Can set the action and object by programme.
Max contact capacity: 3A/240VAC
Can set the action and object by programme.
Max contact capacity:DC30V/50mA
Max output: 24VDC/100mA
Short connect with (COM) valid.
Short connect with (COM) valid.
Short connect with (COM) valid.
Multi function input terminals can be programme set definition. Pls
refer F-01--F-04
Physical type of output signal:0--10V
frequency pulse output, selectable by function F-61/F-62 or switch
J1 J2 J3.
As inverter control signal or feedback signal, can set the act range
and response speed by programme.
VS resistance 89K , AS resistance 250 .
auxiliary
Max output 10VDC/50mA
auxiliary
Common auxiliary power of analog output, analog input signal.
RS485 communication port
Function definition
12
0--20mA
4--20mA

Advertisement