After timer type set you have to go to SETUP line to actually setup the start, the end, the unit mode and water temp setup for
each time band.
SETUP: according to the different timer type selected on the display there will be different lines:
SETUP
F1
Monday
F2
Twesday
Wednesday
TIMER TYPE = 1 (Weekly)
SETUP
F1
Weekly
F2
IMPORTANT NOTE
For the chiller working, the time scheduling setup is always priority on the setup done by keyboard control, except the
remote ON/OFF by digital input
The digital input remote ON/OFF -IF ENABLED- is always priority on time scheduling:
If the unit is in OFF mode by remote (remote ON/OFF) and the time scheduling are enabled the unit remains OFF. When
you switch ON the unit by remote ON/OFF the unit starts to work following the time scheduling setup.
Time scheduling management is disabled even if the configuration mode is activated.
For instance for TIMER TYPE = 0 (daily) in submenu SETUP you have to move on MONDAY line then press ENTER and so
setup for each time band the parameters showed:
TIME BAND 1 ENABLE FLAG: this parameter enable/disables the first time band
TIME BAND 1 HOUR: this parameter allows the setting of the start hour of the first time band
TIME BAND 1 MINUTES: this parameter allows the setting of the start minutes
(from 0 to 59 inside the time band hour) of the first time band.
24
MONITORING SYSTEM - User setting
TIMER TYPE = 0 (Daily)
01/03
SETUP
F1
Thursday
F2
Friday
Saturday
01/01
02/03
F1
F2
TIMER TYPE = 3 (Week-end 5+2)
SETUP
F1
Monday - Friday
F2
Saturday - Sunday
F1
F2
F1
F2
F1
F2
SETUP
03/03
Sunday
01/01
MONDAY
01/24
Time band 1
enable flag
SI
MONDAY
02/24
Time band 1
HOUR
15 h
MONDAY
03/24
Time band 1
MINUTES
25 Min