ADF10S48B
AC-DC Converter Technical Manual V1.1

Qualification Testing

Parameter
Highly accelerated life
test (HALT)
Temperature Humidity
Bias (THB)
High Temperature
Operation Bias (HTOB)
Power and Temperature
Cycling Test (PTC)

Thermal Consideration

Thermal Test Point
Sufficient airflow should be provided to ensure reliable operating of the module. Therefore, thermal
components are mounted on the top surface of the module to dissipate heat to the surrounding
environment by conduction, convection, and radiation. Proper airflow can be verified by measuring the
temperature at the middle of the baseplate.
Middle of the baseplate
Figure 42: Thermal test point
Power Dissipation
The module power dissipation is calculated based on efficiency. The following formula reflects the
relationship between the consumed power (P
GLOBAL ENERGY EFFICIENCY SPECIALIST
Units
Condition
Low temperature limit: –60°C; high temperature limit: 110°C;
6
vibration limit: 40 G; temperature change rate: 40°C per
minute; vibration frequency range: 10–10000 Hz
Maximum input voltage; 85°C; 85% RH; 1000 operating hours under
12
lowest load power
Rated input voltage; airflow rate: 0.5 m/s (100 LFM) to 5 m/s (1000
12
LFM); ambient temperature between +45°C and +55°C; 1000
operating hours; 50% to 80% load
Rated input voltage; airflow rate: 0.5 m/s (100 LFM) to 5 m/s (1000
LFM); ambient temperature between –40°C and +85°C; 1000
12
operating hours; 50% load; temperature change rate: 15°C per
minute; dwell time: 22 minutes
), efficiency (ŋ), and output power (P
d
(1 – ŋ)/ŋ
): P
= P
o
d
o
22