Product version: 1.1
Table 42. Breaker close/trip circuit monitoring TCSSCBR
Function
Operate time delay
Control
Table 43. Synchronizing, synchrocheck and energizing check SESRSYN
Function
Phase shift, j
- j
line
bus
Voltage ratio, U
/U
bus
line
Frequency difference limit between
bus and line
Phase angle difference limit
between bus and line
Voltage difference limit between
bus and line
Time delay output for synchrocheck (0.000-60.000) s
Time delay for energizing check
Closing time for the circuit breaker
Range or value
(0.020 - 300.000) s
Range or value
(-180 to 180) degrees
0.2 to 5.0
(0.003-1.000) Hz
(5.0-90.0) degrees
(0.000-60.000) s
(0.000-60.000) s
1MRK 511 249-BEN -
Issued: February 2011
Accuracy
± 0,5% ± 110 ms
Accuracy
-
-
± 2.0 mHz
± 2.0 degrees
± 0.5% of U
r
± 0.5% ± 25 ms
± 0.5% ± 25 ms
± 0.5% ± 25 ms