ABB REC650 Product Manual page 48

Bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Bay control REC650
Product version: 1.1
Table 16. Electromagnetic compatibility tests, continued
Description
Power frequency immunity
test
• Common mode
• Differential mode
Voltage dips and short
interruptions
Electromagnetic emission
tests
• Conducted, RF-emission
(mains terminal)
0.15...0.50 MHz
0.5...30 MHz
• Radiated RF-emission
30...230 MHz
230...1000 MHz
48
Type test value
300 V rms
150 V rms
Dips:
40%/200 ms
70%/500 ms
Interruptions:
0-50 ms: No restart
0...∞ s : Correct behaviour at
power down
< 79 dB(µV) quasi peak
< 66 dB(µV) average
< 73 dB(µV) quasi peak
< 60 dB(µV) average
< 40 dB(µV/m) quasi peak,
measured at 10 m distance
< 47 dB(µV/m) quasi peak,
measured at 10 m distance
1MRK 511 249-BEN -
Issued: February 2011
Reference
IEC 60255-22-7, class A
IEC 61000-4-16
IEC 60255-11
IEC 61000-4-11
EN 55011, class A
IEC 60255-25
ABB

Hide quick links:

Advertisement

Table of Contents
loading